Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2023171
Status: Active
Facility Name: Roseland Marathon
Address: 2 West 111th Street
Chicago, IL 60628
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X002169
Green Tag Issue Date: 9/30/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Mohammed Zahir
Owner Address: 2 W. 111th Street
Chicago, IL 60628
Owner Status: Current Owner
Purchase Date: 2/14/2008
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 4/17/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 2/10/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0030411 Zahir, Mohammed Current Owner 2/14/2008
U0034659 Roseland Gas & Food Corporation Former Owner 2/20/2008
U0027493 Amoco Oil Company Former Owner
U0000552 BP Products North America, Inc. Former Owner

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00346-2024UPG Upgrade Approved / Issued 3/27/2024 3/28/2024 9/30/2024 Documents

Deficiencies (Current)

NOV Number: E0020240127 (Pending)    Issue Date: 1/11/2024    Expiration Date: 3/11/2024    View NOV Form

Tanks Deficiency
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 2, 3 Annual leak detection certification not completed (Required annually). - Failed Test on 1/2/2024.
1, 2 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - The Covers do not keep water out. Premium STP Sump and Regular STP Sump (T2)
Facility Financial responsibility must be reported yearly - https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility
1, 2, 3 Line interstitial sensor functional test not accomplished (Required annually). - Dispenser Sump Sensors
1, 2, 3 Line leak detection equipment in alarm or failed test, must repair or replace. - All Sensors are in alarm
Facility Missing copies of Annual Walkthrough Inspection Report.
1, 2, 3 Overfill prevention equipment inspection(s) not completed (Required every 3 years).
1, 2, 3 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
1, 2, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
1 Spill prevention equipment failed triennial testing. Must be repaired or replaced.
1, 2, 3 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - STP Sumps and Dispenser Sumps. Failed test on 1/2/2024
1, 2, 3 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Remove Water from STP Sumps.
1, 2, 3 Water in dispenser containment with interstitial sensors - Remove water and repair containments to prevent water ingress - Remove water from Dispenser Sump 1/2 & 5/6

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
08-0184 Eligible 3/28/2008 4/18/2008 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline - Premium Currently in use Federal $0.00
2 10000 Gasoline - Regular Currently in use Federal $0.00
3 12000 Gasoline - Regular Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

No Forms Found