Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2022781
Status: Active
Facility Name: BP
Address: 1329 E. Golf Rd.
Schaumburg, IL 60173
County: Cook
Property Parcel: 07-13-100-026-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X001473
Green Tag Issue Date: 4/19/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: 1329 Golf Real Estate, Inc.
Owner Address: 1329 E. Golf Rd.
Schaumburg, IL 60173
Owner Status: Current Owner
Purchase Date: 3/22/2023
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 4/27/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 4/19/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040873 1329 Golf Real Estate, Inc. Current Owner 3/22/2023
U0037031 Combined Properties, LLC Former Owner 9/18/2013
U0032360 Angel Associates, LP Former Owner 12/17/2009
U0027493 Amoco Oil Company Former Owner
U0000552 BP Products North America, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241296 (Pending)    Issue Date: 5/2/2024    Expiration Date: 7/1/2024    View NOV Form

Tanks Deficiency
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable

NOV Number: E0020241306 (Pending)    Issue Date: 5/2/2024    Expiration Date: 7/1/2024    View NOV Form

Tanks Deficiency
7 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - When removing sump cover support ring came out with it. Ring needs to be anchored to the concrete
Facility Facility Operation and Maintenance Plan not completed or available. - Facility Operations and Maintenance Plan does not meet requirements of new rules. Go to www.sfm.illinois.gov to download and complete O & M template and maintain completed form on site
Facility Financial responsibility must be reported yearly - Financial Responsibility shall be declared annually; The form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility
Facility Missing copies of 30 day Walkthrough Inspection Report.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures plan shall be maintained on site for viewing and reference as necessary (See Operator Training Rules 176.645). The emergency plan template is available on the OSFM website
Facility Missing list of designated Class A/B & C Operators - Go to www.sfm.illinois.gov (UST Operator Training) to find current information regarding Operator Training requirements, including all relevant forms. Copies of certificates must be kept on site
6, 7, 8 Required monthly tank leak test records not available.
6, 7, 8 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
91-2681 9/20/1991 Removal Log

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 500 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/1/1991
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/1/1991
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/1/1991
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/1/1991
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 12000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/1/1991
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/31/1991 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/2/1991

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 3/13/2024 3/13/2027
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/13/2024 3/13/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/13/2024 3/13/2025
Overfill Prev Device Overfill Drop Tube Valve 2/2/2022 2/2/2025
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Discriminating Sump Sensor 3/5/2021 3/5/2022
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A
Spill Contain Device Single Wall Spill Bucket 2/2/2022 2/2/2025
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 7

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/31/1991 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/2/1991

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 3/13/2024 3/13/2027
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/13/2024 3/13/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/13/2024 3/13/2025
Overfill Prev Device Overfill Drop Tube Valve 2/2/2022 2/2/2025
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Discriminating Sump Sensor 3/5/2021 3/5/2022
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A
Spill Contain Device Single Wall Spill Bucket 2/2/2022 2/2/2025
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 8

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/31/1991 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/2/1991

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 3/13/2024 3/13/2027
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/13/2024 3/13/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/13/2024 3/13/2025
Overfill Prev Device Overfill Drop Tube Valve 3/25/2022 3/25/2025
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Discriminating Sump Sensor 3/5/2021 3/5/2022
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A
Spill Contain Device Single Wall Spill Bucket 2/2/2022 2/2/2025
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found