Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2022729
Status: Active
Facility Name: DOM Enterprise of Illinois, Inc.
Address: 6600 W. 95th Street
Oak Lawn, IL 60453
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002496
Green Tag Issue Date: 6/7/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: DOM Enterprise of Illinois, Inc.
Owner Address: 6600 W. 95th Street
Oak Lawn, IL 60453
Owner Status: Current Owner
Purchase Date: 4/25/2004
Type of Financial Responsibility: Letter of Credit
Financial Responsibility Reporting Due Date: 12/13/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 6/7/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0033764 DOM Enterprise of Illinois, Inc. Current Owner 4/25/2004
U0027042 TGS New Enterprises Limited, LLC Former Owner 6/17/2002
U0008299 Kean Bros, Inc. Former Owner 9/30/1995

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241099 (Pending)    Issue Date: 4/12/2024    Expiration Date: 6/11/2024    View NOV Form

Tanks Deficiency
5, 6, 7 Annual leak detection certification not completed (Required annually). - LAST TEST WAS 3-29-23
6, 7 Annual line precision and mechanical line leak detector functional test not completed. - LAST TEST WAS 3-29-23
7 Drop tube valve or overfill alarm failed inspection. Repair or replace equipment. - FAILED INSPECTION ON 4-9-24
5, 6, 7 Line interstitial sensor functional test not accomplished (Required annually). - LAST TEST WAS 3-29-23
6 Miscellaneous - FAILED CONTAINMENT TESTING ON 4-9-24
5, 6, 7 Triennial spill prevention equipment testing not completed. - LAST TEST WAS 3-25-21
5, 7 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - LAST TEST WAS 3-25-21

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
95-2030 9/28/1995 Removal Log

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
95-2030 Eligible 10/16/1995 11/8/1995 $10,000
95-2030 Returned 5/9/2003 5/28/2003 $Not Selected
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 9/28/1995
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 18 Abandoned Date:
Install Date: 5/5/1977 Red Tag Issue Date:
Last Used Date: 9/28/1995 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 9/28/1995
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 18 Abandoned Date:
Install Date: 5/5/1977 Red Tag Issue Date:
Last Used Date: 9/28/1995 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 9/28/1995
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 18 Abandoned Date:
Install Date: 5/5/1977 Red Tag Issue Date:
Last Used Date: 9/28/1995 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 550 Petroleum Use:
Product: Motor Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 9/28/1995
OSFM First Notify Date: 10/17/1995 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 1/1/1973 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 15000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/23/1998 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: 9/30/1995 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/30/1995

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/9/2024 4/9/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300 with CSLD 4/9/2024 4/9/2025
Overfill Prev Device Overfill Drop Tube Valve 3/29/2023 3/29/2026
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 4/9/2024 4/9/2027
Leak Detect - Piping Sump Sensor 4/9/2024 4/9/2025
Spill Contain Device Single Wall Spill Bucket 4/9/2024 4/9/2027
Tank Composite Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 3/25/2021
Piping Flexible Double Wall Environ Geo Flex Precision Test Pass 4/9/2024
Tank Composite Single Wall Precision Test (Tank) Pass 1/4/2024



Tank Number 6

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/23/1998 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: 9/30/1995 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/30/1995

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/9/2024 4/9/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300 with CSLD 4/9/2024 4/9/2025
Overfill Prev Device Overfill Drop Tube Valve 3/29/2023 3/29/2026
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 4/19/2024 4/19/2027
Leak Detect - Piping Sump Sensor 4/9/2024 4/9/2025
Spill Contain Device Single Wall Spill Bucket 4/9/2024 4/9/2027
Tank Composite Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 3/25/2021
Piping Flexible Double Wall Environ Geo Flex Precision Test Pass 4/9/2024



Tank Number 7

Capacity: 6000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/9/2007 Abandoned Material:
Current Age: 16 Abandoned Date:
Install Date: 11/6/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/6/2007

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/9/2024 4/9/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300 with CSLD 4/9/2024 4/9/2025
Overfill Prev Device Overfill Drop Tube Valve 4/19/2024 4/19/2027
Piping Flexible Double Wall Total Containment Omniflex II N/A N/A
Piping Single Wall STP/Tanktop Sump 4/9/2024 4/9/2027
Leak Detect - Piping Sump Sensor 4/9/2024 4/9/2025
Spill Contain Device Single Wall Spill Bucket 4/9/2024 4/9/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Environ Geo Flex Precision Test Pass 3/25/2021
Piping Flexible Double Wall Total Containment Omniflex II Precision Test Pass 4/9/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/9/2024 4/9/2027
Leak Detect - Piping Sump Sensor 4/9/2024 4/9/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found