Deficiencies (Current)
NOV Number:
E0020241227
(Pending)
Issue Date:
4/24/2024
Expiration Date:
6/23/2024
View NOV Form
Tanks |
Deficiency |
Facility |
Missing copies of 30 day Walkthrough Inspection Report. - 30 day reports are missing since 2022. Need to keep records of maintenance of UST system. |
4, 5, 6 |
Precision tank test required. - If cannot provide 2 years of passing monthly tank records. |
4, 5, 6 |
Required monthly tank leak test records not available. |
4 |
Tank monitor does not appear to function properly and requires maintenance. - Tank #1 is not currently being monitored for leak test. Missing CSLD results from malfuntioning probe. Only takes fuel levels. Need to repair and recertify monitor for tank #1 |