Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2021198
Status: Active
Facility Name: Circle K #6720
Address: 681 Terra Cotta Avenue
Crystal Lake, IL 60014
County: McHenry
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X003312
Green Tag Issue Date: 6/23/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: RDK Ventures, LLC
Owner Address: 1100 Situs Court, Suite 100
Raleigh, NC 27606
Owner Status: Current Owner
Purchase Date: 1/7/2010
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/27/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 6/23/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035671 RDK Ventures, LLC Current Owner 1/7/2010
U0013849 Shell Oil Products Former Owner 12/31/1967
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner
U0027449 Equilon Enterprises, LLC Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241027 (Pending)    Issue Date: 4/9/2024    Expiration Date: 6/8/2024    View NOV Form

Tanks Deficiency
5, 7 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Section 175.410 Submersible, Under-dispenser, Transition and Other Containment Sumps a) All containment sumps must consist of a factory manufactured containment that is liquid-tight on its sides, bottom and at any penetrations and is compatible with the substance conveyed by the piping. Such containment shall also have a factory manufactured protective cover and supporting components that are properly maintained. If the protective cover or its supporting components are cracked, deteriorated or missing, the cover and supporting components that are defective shall be replaced. SPECIFICALLY THE ATG COVERS ARE CONCRETED ON TO THE TANK PAD AND NEED TO BE ACCESSIBLE.
5, 6, 7 Dispensers - hoses cracked, split or worn and require replacement - REPLACE MAIN HOSE.
Facility Missing copies of current testing certificates for operator training - Copies of all current Class A/B testing certificates shall be maintained on file on site. Copies of all current Class C testing certificates shall be maintained on file on site. Go to www.sfm.illinois.gov (UST Operator Training) to find current information regarding Operator Training requirements, including all relevant forms.
Facility Missing list of designated Class A/B & C Operators - A comprehensive list of Class A / B / C Operator(s) shall be maintained on site and must be current.
5, 6, 7 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
5, 6, 7 Tank monitor does not appear to function properly and requires maintenance. - Indicator GREEN light on panel of Veeder-Root ATG is not functional. Replace as necessary to provide proper operation.

NOV Number: E0020241030 (Pending)    Issue Date: 4/9/2024    Expiration Date: 6/8/2024    View NOV Form

Tanks Deficiency
Facility Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser - Section 175.210g; All dispensing units shall be readily visible from the control station without assistive devices. If view is permanently obstructed, or the dispenser is located so that activity is not readily visible, closed-circuit cameras that provide a view of each side of the dispensing unit and project an image on a screen at least 6 inches in diagonal located at the control station may be used.
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 12000 Gasoline Removed Federal $0.00 08/01/1989 - REM
2 12000 Gasoline Removed Federal $0.00 08/01/1989 - REM
3 12000 Gasoline Removed Federal $0.00 08/01/1989 - REM
4 550 Used Oil Removed Federal $0.00 08/01/1989 - REM
5 12000 Gasoline - Regular Currently in use Federal
6 12000 Diesel Fuel Currently in use Federal
7 12000 Gasoline - Premium Currently in use Federal

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active

MFD Motorfuel Dispensing Forms

No Forms Found