Deficiencies (Current)
NOV Number:
E0020240888
(Pending)
Issue Date:
3/26/2024
Expiration Date:
5/25/2024
View NOV Form
Tanks |
Deficiency |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom. 175.210 h) |
NOV Number:
E0020240889
(Pending)
Issue Date:
3/26/2024
Expiration Date:
5/25/2024
View NOV Form
Tanks |
Deficiency |
4, 5 |
Dispensers - hoses cracked, split or worn and require replacement - Replace main hose(s) on the above listed dispenser(s). |
4, 5 |
Piping interstitial must be open in all sumps - 175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps. Valves in STP sumps appear to be closed. |
4, 5 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Spill Bucket(s) contain(s) liquid and/or debris; remove liquid/debris and maintain clean and dry at all times. |