Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2021150
Status: Active
Facility Name: Circle K #6772
Address: 1597 West Irving Park Road
Hanover Park, IL 60103
County: Du Page
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X000754
Green Tag Issue Date: 1/28/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: RDK Ventures, LLC
Owner Address: 1100 Situs Court, Suite 100
Raleigh, NC 27606
Owner Status: Current Owner
Purchase Date: 1/7/2010
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/27/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 3/28/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035671 RDK Ventures, LLC Current Owner 1/7/2010
U0013849 Shell Oil Products Former Owner 12/31/1967
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner
U0027449 Equilon Enterprises, LLC Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020240888 (Pending)    Issue Date: 3/26/2024    Expiration Date: 5/25/2024    View NOV Form

Tanks Deficiency
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom. 175.210 h)

NOV Number: E0020240889 (Pending)    Issue Date: 3/26/2024    Expiration Date: 5/25/2024    View NOV Form

Tanks Deficiency
4, 5 Dispensers - hoses cracked, split or worn and require replacement - Replace main hose(s) on the above listed dispenser(s).
4, 5 Piping interstitial must be open in all sumps - 175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps. Valves in STP sumps appear to be closed.
4, 5 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Spill Bucket(s) contain(s) liquid and/or debris; remove liquid/debris and maintain clean and dry at all times.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
06-0314 3/13/2006 Removal Log 00263-2006REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
03-0492 Eligible 5/1/2003 5/15/2003 $10,000
06-0314 Eligible 9/21/2006 9/29/2006 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline Removed Federal $0.00 03/13/2006 - REM
2 10000 Gasoline Removed Federal $0.00 03/13/2006 - REM
3 10000 Gasoline Removed Federal $0.00 03/13/2006 - REM
4 20000 Gasoline - Regular Currently in use Federal $0.00
5 12000 Gasoline - Premium Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
11/12 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active

MFD Motorfuel Dispensing Forms