Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2021115
Status: Active
Facility Name: Circle K #6734
Address: 50 West Lake Cook Road & Route 83
Buffalo Grove, IL 60089
County: Lake
Property Parcel: 15-33-305-002
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X003399
Green Tag Issue Date: 4/14/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: RDK Ventures, LLC
Owner Address: 1100 Situs Court, Suite 100
Raleigh, NC 27606
Owner Status: Current Owner
Purchase Date: 1/7/2010
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/27/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 4/14/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035671 RDK Ventures, LLC Current Owner 1/7/2010
U0013849 Shell Oil Products Former Owner 12/31/1967
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner
U0027449 Equilon Enterprises, LLC Former Owner

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00597-2024LIN Lining Inspection Approved / Issued 5/15/2024 5/16/2024 11/18/2024 Documents

Deficiencies (Current)

NOV Number: E0020240883 (Pending)    Issue Date: 3/22/2024    Expiration Date: 5/21/2024    View NOV Form

Tanks Deficiency
1, 2, 3 Dispensers - hoses cracked, split or worn and require replacement
2 Line interstitial sensors have been raised and rendered inoperational. - STP Interstitial sensor(s) are not functioning effectively. Place sensors vertically at the lowest point in the sump. (Per 175.410. 2.A.ii)
1, 2, 3 Piping interstitial must be open in all sumps - Remove jumper tubing or place tubing in orientation to allow liquid to leave secondary piping and enter sump. (Per 175.420.b(b).)
1, 2, 3 Tank internal lining inspection past due (Required every 5 years).

NOV Number: E0020241074 (Pending)    Issue Date: 4/11/2024    Expiration Date: 6/10/2024    View NOV Form

Tanks Deficiency
1 Miscellaneous - ATG failed testing. Repair/Replace Probe.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
03-0422 Eligible 6/2/2003 7/3/2003 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/24/1986 Abandoned Material:
Current Age: 45 Abandoned Date:
Install Date: 1/1/1979 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Lining Materials Internal 3/21/2019 3/21/2024
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Other Non-vented check valve N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R with CSLD 4/13/2023 4/4/2024
Overfill Prev Device Overfill Drop Tube Valve 6/21/2022 6/21/2025
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 4/16/2024 4/16/2027
Leak Detect - Piping Stand Alone Sump Sensor Non-Discriminating 6/9/2021 6/9/2022
Leak Detect - Piping Sump Sensor 4/13/2023 4/13/2024
Leak Detect - Piping Sump Sensor with positive shutdown 4/4/2024 4/4/2025
Spill Contain Device Single Wall Spill Bucket 4/29/2021 4/29/2024
Tank Fiberglass Single Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test Pass 4/13/2023



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/24/1986 Abandoned Material:
Current Age: 45 Abandoned Date:
Install Date: 1/1/1979 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Lining Materials Internal 3/21/2019 3/21/2024
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/4/2024 4/4/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R with CSLD 4/4/2024 4/4/2025
Overfill Prev Device Overfill Drop Tube Valve 6/21/2022 6/21/2025
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 4/16/2024 4/16/2027
Leak Detect - Piping Sump Sensor 4/13/2023 4/13/2024
Leak Detect - Piping Sump Sensor with positive shutdown 4/4/2024 4/4/2025
Spill Contain Device Single Wall Spill Bucket 4/29/2021 4/29/2024
Tank Fiberglass Single Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test Pass 4/13/2023



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/24/1986 Abandoned Material:
Current Age: 45 Abandoned Date:
Install Date: 1/1/1979 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Lining Materials Internal 3/21/2019 3/21/2024
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/4/2024 4/4/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R with CSLD 4/4/2024 4/4/2025
Overfill Prev Device Overfill Drop Tube Valve 6/21/2022 6/21/2025
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 4/16/2024 4/16/2027
Leak Detect - Piping Non-Discriminating Sump Sensor 5/12/2022 5/12/2023
Leak Detect - Piping Sump Sensor with positive shutdown 4/4/2024 4/4/2025
Spill Contain Device Single Wall Spill Bucket 4/29/2021 4/29/2024
Tank Fiberglass Single Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test Pass 4/4/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/16/2024 4/16/2027
Leak Detect - Piping Stand Alone Sump Sensor 4/4/2024 4/4/2025



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/16/2024 4/16/2027
Leak Detect - Piping Stand Alone Sump Sensor 4/4/2024 4/4/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/16/2024 4/16/2027
Leak Detect - Piping Stand Alone Sump Sensor 4/4/2024 4/4/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/16/2024 4/16/2027
Leak Detect - Piping Stand Alone Sump Sensor 4/4/2024 4/4/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/16/2024 4/16/2027
Leak Detect - Piping Stand Alone Sump Sensor 4/4/2024 4/4/2025



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/16/2024 4/16/2027
Leak Detect - Piping Stand Alone Sump Sensor 4/4/2024 4/4/2025

MFD Motorfuel Dispensing Forms

No Forms Found