Deficiencies (Current)
NOV Number:
E0020240883
(Pending)
Issue Date:
3/22/2024
Expiration Date:
5/21/2024
View NOV Form
Tanks |
Deficiency |
1, 2, 3 |
Dispensers - hoses cracked, split or worn and require replacement |
2 |
Line interstitial sensors have been raised and rendered inoperational. - STP Interstitial sensor(s) are not functioning effectively. Place sensors vertically at the lowest point in the sump. (Per 175.410. 2.A.ii) |
1, 2, 3 |
Piping interstitial must be open in all sumps - Remove jumper tubing or place tubing in orientation to allow liquid to leave secondary piping and enter sump. (Per 175.420.b(b).) |
1, 2, 3 |
Tank internal lining inspection past due (Required every 5 years). |
NOV Number:
E0020241074
(Pending)
Issue Date:
4/11/2024
Expiration Date:
6/10/2024
View NOV Form
Tanks |
Deficiency |
1 |
Miscellaneous - ATG failed testing. Repair/Replace Probe. |