Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2020659
Status: Active
Facility Name: Elburn Real Estate, LLC
Address: 213 S. Main Street
Elburn, IL 60119
County: Kane
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X003291
Green Tag Issue Date: 4/21/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Elburn Real Estate, LLC
Owner Address: 213 S. Main Street
Elburn, IL 601199119
Owner Status: Current Owner
Purchase Date: 6/1/2009
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 1/26/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 4/21/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035867 Elburn Real Estate, LLC Current Owner 6/1/2009
U0032209 Combined Real Estate, LLC Former Owner 7/29/2004
U0007721 J & L Oil Co., Inc. Former Owner 6/1/1968

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00004-2024UPG Upgrade Cancelled by Contractor 1/2/2024 1/2/2024 7/2/2024 Documents

Deficiencies (Current)

NOV Number: E0020240590 (Pending)    Issue Date: 2/29/2024    Expiration Date: 4/29/2024    View NOV Form

Tanks Deficiency
Facility A/B operator retraining required as a result of issuance of the Notice of Violation - Primary A / B certified operator shall be retrained as a result of NOV being issued.
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Emergency shutoff switch shall be tested annually. Perform test, complete testing form (form is available at www.sfm.illinois.gov) and maintain on site with other annual testing documentation.
Facility Miscellaneous - EMERGENCY STOP SWITCH IS NOT EASILY ACCESSIBLE, REMOVE RACK TO PROVIDE ACCESS IN THE EVENT OF AN EMERGENCY.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and 2 years documentation maintained on site.
Facility Missing copies of current testing certificates for operator training - Copies of all current Class A/B testing certificates shall be maintained on file on site. Copies of all current Class C testing certificates shall be maintained on file on site. Go to www.sfm.illinois.gov (UST Operator Training) to find current information regarding Operator Training requirements, including all relevant forms.
Facility Missing list of designated Class A/B & C Operators - A comprehensive list of Class A / B / C Operator(s) shall be maintained on site and must be current.
1, 2, 3, 4 Monthly line interstitial sensor records not available. - Maintain one NORMAL report per LINE, per month, from ATG. Must maintain 24 months’ worth.
1, 2, 3, 4 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Must maintain 2 years of inspection reports.
1, 2, 3, 4 Tank monitor does not appear to function properly and requires maintenance. - Indicator light(green) on panel of Veeder-Root ATG is not functional. Replace as necessary to provide proper operation.

NOV Number: E0020240591 (Pending)    Issue Date: 2/29/2024    Expiration Date: 4/29/2024    View NOV Form

Tanks Deficiency
Facility Code complying instruction/warning signs are not properly mounted at each dispenser island - Self-service instructional signs at dispensers are missing or do not meet minimum requirements. Install appropriate signage.
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers.
Facility LP gas storage lacks proper collision protection or a 40" measurement from cabinet to a 5" raised sidewalk - The distance of any LP gas storage cabinet from any opening into any building, including any doorway or window, shall not be less than 5 feet, or in the event there is only one point of egress out of the building, shall not be less than 10 feet.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
96-2013 Eligible 7/22/2004 8/10/2004 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline - Premium Currently in use Federal $0.00
2 10000 Gasoline - Regular Currently in use Federal $0.00
3 6000 Gasoline - Regular Currently in use Federal $0.00
4 4000 Diesel Fuel Currently in use Federal $0.00
5 2000 Gasoline Does Not Exist Federal $0.00
6 4000 Gasoline Removed Federal $0.00 09/01/1998 - REM
7 1000 Kerosene Removed Federal $0.00 09/01/1996 - REM
8 1000 Heating Oil Does Not Exist State $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active

MFD Motorfuel Dispensing Forms

No Forms Found