Deficiencies (Current)
NOV Number:
E0020241222
(Pending)
Issue Date:
4/24/2024
Expiration Date:
6/23/2024
View NOV Form
Tanks |
Deficiency |
1, 2, 3, 4 |
Annual piping impressed current test not completed. |
3 |
Install or replace lockable fill pipe caps. - Fill snap cap is broke. Repair/Replace cap. (Premium East) |
2, 3 |
Miscellaneous - Repair/replace possible leaking tanks. |
Facility |
Missing copies of 30 day Walkthrough Inspection Report. - Need to fill out completely. |
2, 3, 4 |
Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Shear valves/Impact valves. Provide documentation that annual testing of all shear valves has been conducted and passed. Go to https://sfm.illinois.gov to print out the Shear Valve inspection form. |
4 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Spill bucket filled to top with water. |
NOV Number:
E0020241225
(Pending)
Issue Date:
4/24/2024
Expiration Date:
6/23/2024
View NOV Form
Tanks |
Deficiency |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h) |