Facility |
Facility Operation and Maintenance Plan not completed or available. - Facility Operations and Maintenance Plan is available at https://sfm.illinois.gov to download and complete. Maintain documentation on site. |
Facility |
Financial responsibility must be reported yearly - Financial Responsibility form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility. |
Facility |
Missing copies of 30 day Walkthrough Inspection Report. - Need to fill out completely. (Dates) |
7, 8 |
Monthly line interstitial sensor records not available. - Maintain one NORMAL report per LINE, per month, from ATG. Must maintain 24 months’ worth. (Liquid Status) |
3, 5, 7, 8 |
Precision tank test required. - Due to missing tank leak tested records. |
7, 8 |
Required monthly tank interstitial sensor records not available. - Maintain one NORMAL report per TANK, per month, from ATG. Must maintain 24 months’ worth. (Liquid Status) |
3, 5, 7, 8 |
Required monthly tank leak test records not available. - Maintain one PASSING report per TANK, per month, from ATG. Reference 175.630 c)2)B) (CSLD results) |
7, 8 |
Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Go to https://sfm.illinois.gov to print out the Shear Valve inspection form. |
5, 7, 8 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |