Facility Number: 2017675
Status: Active
Facility Name: Marathon
Address: 711 Halsted Street
Chicago Heights, IL 60411
County: Cook
Property Parcel: 32-16-304-041-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X002897
Green Tag Issue Date: 12/8/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Sohail Khan
Owner Address: 8044 Abbey Ct.
Tinley Park, IL 60477
Owner Status: Current Owner
Purchase Date: 4/28/2009
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/8/2023

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 12/8/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0031138 Khan, Sohail Current Owner 4/28/2009
U0032352 Sam Jean-Pierre Former Owner 5/26/2004
U0029517 V5 Enterprises Inc Former Owner 7/1/2002
U0029861 N E P Operating LLC Former Owner 11/1/2000
U0009782 Martin Oil Marketing, Ltd. Former Owner 9/23/1969
U0026552 Speedway, LLC Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241251 (Pending)    Issue Date: 4/29/2024    Expiration Date: 6/28/2024    View NOV Form

Tanks Deficiency
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - (No Comms)

NOV Number: E0020241252 (Pending)    Issue Date: 4/29/2024    Expiration Date: 6/28/2024    View NOV Form

Tanks Deficiency
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Emergency shutoff switch form is available at https://sfm.illinois.gov. Perform test and complete form. Maintain form on site.
Facility Facility Operation and Maintenance Plan not completed or available. - Facility Operations and Maintenance Plan is available at https://sfm.illinois.gov to download and complete. Maintain documentation on site.
Facility Financial responsibility must be reported yearly - Financial Responsibility form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility.
7 Install or replace lockable fill pipe caps. - Snap cap is broken on E-85 Fill. Repair/Replace
6 Line leak detection equipment in alarm or failed test, must repair or replace. - Tank 6 STP sump sensor failed testing 9/18/2023.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at https://sfm.illinois.gov.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and documentation maintained on site.
Facility Missing copy of emergency instructions or emergency procedures plan - Form is available at https://sfm.illinois.gov to download and complete. Maintain documentation on site.
Facility Missing list of designated Class A/B & C Operators - Form is available at https://sfm.illinois.gov to download and complete. Maintain documentation on site.
5, 6, 7 Monthly line interstitial sensor records not available. - Maintain one NORMAL report per LINE, per month, from ATG. Must maintain 24 months’ worth. (Liquid Status)
6, 7 Open electrical conduit or junction boxes. - Open junction box for Permium/E-85 Interstitial. Repair/Replace.
5, 6, 7 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - All overfill prevention drop tubes failed on 9/18/2023.
5, 6, 7 Piping interstitial must be open in all sumps - Remove jumper tubing and/or Schrader valves in all dispensers and Premium STP sumps.
5, 6, 7 Precision line test required. - Due to missing monthly line leak detection tapes.
5, 6, 7 Precision tank test required. - Due to missing monthly Tank leak detection tapes.
5, 6, 7 Required monthly tank interstitial sensor records not available. - Maintain one NORMAL report per TANK, per month, from ATG. Must maintain 24 months’ worth. (Liquid status)
5, 6, 7 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Shear valves/Impact valves. Provide documentation that annual testing of all shear valves has been conducted and passed. Go to https://sfm.illinois.gov to print out the Shear Valve inspection form.
5, 6, 7 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
09-1137 10/14/2009 Removal Log 01220-2009REM
09-1137 10/13/2009 Removal Log 01220-2009REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
89-1158 Eligible 9/20/1993 11/24/1993 $50,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 12000 Gasoline Removed Federal $0.00 10/14/2009 - REM
2 10000 Gasoline Removed Federal $0.00 10/14/2009 - REM
3 8000 Gasoline Removed Federal $0.00 10/13/2009 - REM
4 4000 Kerosene Removed Federal $0.00 10/13/2009 - REM
5 10000 Gasoline - Regular Currently in use Federal $0.00
6 3000 Gasoline - Premium Currently in use Federal $0.00
7 3000 E85 Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active

MFD Motorfuel Dispensing Forms

No Forms Found