Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2016474
Status: Active
Facility Name: IL0136
Address: 1175 Route 134
Round Lake, IL 60073
County: Lake
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X001655
Green Tag Issue Date: 4/6/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Lehigh Gas Wholesale Services
Owner Address: 645 Hamilton, Suite 400
Allentown, PA 18101
Owner Status: Current Owner
Purchase Date: 9/27/2016
Type of Financial Responsibility: Surety Bond
Financial Responsibility Reporting Due Date: 6/28/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 4/6/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037337 Lehigh Gas Wholesale Services Current Owner 9/27/2016
U0000651 B.A.P.A., LLC & PT, LLC Former Owner 10/23/2014
U0032455 The Premcor Refining Group, Inc. c/o Valero Energy Corporation Former Owner 6/1/2010
U0031662 Apeksha, Inc. Former Owner 8/18/2003
U0029789 Clark Retail Enterprises, Inc. Former Owner 10/24/1994
U0028787 Clark Retail Enterprises, Inc., Former Owner 10/24/1994
U0003073 Clark Retail Enterprises, Inc. Former Owner 10/24/1994
U0000651 B.A.P.A., LLC & PT, LLC Former Owner 12/31/1967
U0025164 BAPA, LLC & PT, LLC Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241383 (Pending)    Issue Date: 5/17/2024    Expiration Date: 7/16/2024   

Tanks Deficiency
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing copies of current testing certificates for operator training - Copies of all current Class C testing certificates shall be maintained on file on site.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures plan shall be maintained on site for viewing and reference as necessary (See Operator Training Rules 176.645). The emergency plan template is available on the OSFM website.
Facility Missing copy of written UST facility operation & maintenance plan - Adopt and implement a written operations and maintenance plan, signed by both the owner and either a Class A or Class B Operator designated for the UST facility An Operations & Maintenance template is available at www.sfm.illinois.gov to download and complete O & M template and maintain completed form on site.
Facility Missing list of designated Class A/B & C Operators
2 Open electrical conduit or junction boxes. - Open electric wiring in STP containment.
1, 2, 3 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
1, 2, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
3 Water in containment without required interstitial sensors - install cathodic protection on all exposed steel. - STP sump(s) contain(s) liquid. Remove liquid and repair containment to prevent further liquid ingress. Must show documentaion showing repairs comleted. (Per 41 Ill Admin code 175.410.h)

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
95-0597 Eligible 8/29/1995 10/2/1995 $10,000
00-1039 Eligible 3/4/2003 3/13/2003 $10,000
95-0597 Eligible 5/2/2003 5/20/2003 $10,000
00-1039 Returned 8/5/2010 9/16/2010 $Not Selected
95-0597 Eligible 8/5/2010 9/16/2010 $10,000
20220576 Eligible 4/3/2024 4/17/2024 $5,000 Letter
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/6/1986 Abandoned Material:
Current Age: 39 Abandoned Date:
Install Date: 4/18/1985 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/18/1985

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 8/21/2019 8/21/2022
Corrosion Prot - Piping Sacrificial Anode Flex Connector 7/13/2022 7/13/2025
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/30/2023 5/30/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/30/2023 5/30/2024
Overfill Prev Device Overfill Drop Tube Valve 9/8/2021 9/8/2024
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Double Wall Spill Bucket 11/4/2021 11/4/2024
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test Pass 5/30/2023



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/6/1986 Abandoned Material:
Current Age: 39 Abandoned Date:
Install Date: 4/18/1985 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/18/1985

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 8/21/2019 8/21/2022
Corrosion Prot - Piping Sacrificial Anode Flex Connector 7/13/2022 7/13/2025
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/30/2023 5/30/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/30/2023 5/30/2024
Overfill Prev Device Overfill Drop Tube Valve 7/22/2021 7/22/2024
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 11/4/2021 11/4/2024
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test Pass 9/12/2023



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/6/1986 Abandoned Material:
Current Age: 39 Abandoned Date:
Install Date: 4/18/1985 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/18/1985

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 8/21/2019 8/21/2022
Corrosion Prot - Piping Sacrificial Anode Flex Connector 7/13/2022 7/13/2025
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/30/2023 5/30/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/30/2023 5/30/2024
Overfill Prev Device Overfill Drop Tube Valve 7/22/2021 7/22/2024
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump 8/17/2023 8/17/2026
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Double Wall Spill Bucket 1/4/2022 1/4/2025
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test Pass 8/18/2023

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found