Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2016462
Status: Inactive
Facility Name: VRG Properties Company
Address: 26025 W. Grand Ave.
Ingleside, IL 60041
County: Lake
Property Parcel: 05-11-403-008
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002901
Green Tag Issue Date: 10/4/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: VRG Properties Company
Owner Address: One Valero Way
San Antonio, TX 78249
Owner Status: Current Owner
Purchase Date: 4/4/2024
Type of Financial Responsibility:
Financial Responsibility Reporting Due Date:

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/25/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037981 VRG Properties Company Current Owner 4/4/2024
U0039514 Aaliyah 44, LLC Former Owner 4/25/2019
U0037337 Lehigh Gas Wholesale Services Former Owner 9/27/2016
U0036950 Gas Cap Fuels Former Owner 4/12/2013
U0025164 BAPA, LLC & PT, LLC Former Owner 9/30/2012
U0033249 CCH Enterprise, LLC Former Owner 12/1/2005
U0031597 AK Corporation Former Owner 8/19/2003
U0031516 AK Business Enterprises, LLC Former Owner 8/19/2003
U0024983 Clark Refining & Marketing, Inc. Former Owner 1/9/1996
U0032455 The Premcor Refining Group, Inc. c/o Valero Energy Corporation Former Owner 2/1/1995
U0000651 B.A.P.A., LLC & PT, LLC Former Owner 12/31/1967
U0029789 Clark Retail Enterprises, Inc. Former Owner
U0028787 Clark Retail Enterprises, Inc., Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241206 (Pending)    Issue Date: 4/23/2024    Expiration Date: 6/22/2024    View NOV Form

Tanks Deficiency
2, 3 Impressed current system failed test or appears non operational. Must repair. - Power turned off to rectifier.
2, 3 Monthly impressed current log not available or maintained. - A log showing the rectifier gauge readings from Impressed Current rectifier shall be maintained monthly on site. Log shall show date; amp, volt, and hour meter readings; including the initials of the employee who recorded information.
1, 2, 3 Submit Notification Form For Tank Status Change - Submit OSFM Notification Form placing all tanks in Temporarily Out of Use status. The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of a tank status change.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
99-0519 Eligible 5/31/2000 6/23/2000 $10,000
99-0519 Eligible 9/23/2003 10/6/2003 $10,000
99-0519 Eligible 4/1/2005 1/24/2006 $10,000
99-0519 Eligible 1/23/2006 2/24/2006 $10,000
99-0519 Eligible 9/10/2012 10/24/2012 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Out of service CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/6/1986 Abandoned Material:
Current Age: 47 Abandoned Date:
Install Date: 1/1/1977 Red Tag Issue Date:
Last Used Date: 4/23/2024 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/30/2024 1/30/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 1/30/2024 1/30/2025
Overfill Prev Device Overfill Drop Tube Valve 12/3/2021 12/3/2024
Piping Flexible Double Wall NUPI Smartflex N/A N/A
Piping Single Wall STP/Tanktop Sump 12/3/2021 12/3/2024
Leak Detect - Piping Discriminating Sump Sensor 3/3/2021 3/3/2022
Leak Detect - Piping Sump Sensor with positive shutdown 1/30/2024 1/30/2025
Spill Contain Device Single Wall Spill Bucket 12/3/2021 12/3/2024
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Tank Fiberglass Single Wall Precision Test (Tank) Pass 10/20/2021



Tank Number 2

Capacity: 5000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Out of service CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/6/1986 Abandoned Material:
Current Age: 47 Abandoned Date:
Install Date: 1/1/1977 Red Tag Issue Date:
Last Used Date: 4/23/2024 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 1/30/2024 1/30/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/30/2024 1/30/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 1/30/2024 1/30/2025
Overfill Prev Device Ball Float Vent Valve Universal 37 12/3/2021 12/3/2024
Overfill Prev Device Overfill Drop Tube Valve 12/3/2021 12/3/2024
Piping Flexible Double Wall NUPI Smartflex N/A N/A
Piping Single Wall STP/Tanktop Sump 12/3/2021 12/3/2024
Leak Detect - Piping Discriminating Sump Sensor 3/3/2021 3/3/2022
Leak Detect - Piping Sump Sensor with positive shutdown 1/30/2024 1/30/2025
Spill Contain Device Single Wall Spill Bucket 12/3/2021 12/3/2024
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Tank Steel Single Wall Precision Test (Tank) Pass 10/20/2021



Tank Number 3

Capacity: 4000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Out of service CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/6/1986 Abandoned Material:
Current Age: 47 Abandoned Date:
Install Date: 1/1/1977 Red Tag Issue Date:
Last Used Date: 4/23/2024 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 1/30/2024 1/30/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/30/2024 1/30/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 1/30/2024 1/30/2025
Overfill Prev Device Ball Float Vent Valve Universal 37 12/3/2021 12/3/2024
Piping Flexible Double Wall NUPI Smartflex N/A N/A
Piping Single Wall STP/Tanktop Sump 12/3/2021 12/3/2024
Leak Detect - Piping Discriminating Sump Sensor 3/3/2021 3/3/2022
Leak Detect - Piping Sump Sensor with positive shutdown 1/30/2024 1/30/2025
Spill Contain Device Single Wall Spill Bucket 12/3/2021 12/3/2024
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Tank Steel Single Wall Precision Test (Tank) Pass 10/20/2021

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/3/2021 12/3/2024
Leak Detect - Piping Sump Sensor with positive shutdown 1/30/2024 1/30/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/3/2021 12/3/2024
Leak Detect - Piping Sump Sensor with positive shutdown 1/30/2024 1/30/2025

MFD Motorfuel Dispensing Forms

No Forms Found