Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2016460
Status: Active
Facility Name: True North Location 3063
Address: 905 W. Illinois
Aurora, IL 60506
County: Kane
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X003238
Green Tag Issue Date: 10/25/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Hanif Malik
Owner Address: 905 W. Illinois
Aurora, IL 60506
Owner Status: Current Owner
Purchase Date: 5/16/2000
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 11/13/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 10/25/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0029619 Malik, Hanif Current Owner 5/16/2000
U0013849 Shell Oil Products Former Owner 10/15/1993
U0027449 Equilon Enterprises, LLC Former Owner 6/13/1988
U0000651 B.A.P.A., LLC & PT, LLC Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241158 (Pending)    Issue Date: 4/18/2024    Expiration Date: 6/17/2024    View NOV Form

Tanks Deficiency
Facility Code complying instruction/warning signs are not properly mounted at each dispenser island - 175.210 Attended self-service motor fuel dispensing facilities and islands O) Minimum signage 1), 2), 3), 4), and 5). Warning signs are required at all dispensers.

NOV Number: E0020241159 (Pending)    Issue Date: 4/18/2024    Expiration Date: 6/17/2024    View NOV Form

Tanks Deficiency
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain on site with other annual testing documentation.
6 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
6 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
7 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
7 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
8 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
8 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
6, 7, 8 Document that emergency shut-off (shear valves) are in proper working order - Provide documentation that annual testing of all shear valves has been conducted and passed.
7 Install drop tube vlave. - Regular south has stick in drop tube. Stick must be removed and make sure overfill drop tube valve is not damaged.
6, 7, 8 Line interstitial sensor functional test not accomplished (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
Facility Miscellaneous - Emergency shut off switch at control station is blocked with tobacco products. Display must be moved or emergency shut off switch moved to an open unobstructed location.
Facility Miscellaneous - Emergency shut off switch must have a sign stating "Fuel Emergency Shut Off" with letters 2" in height.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and documentation maintained on site.
6, 7, 8 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Spill buckets must be kept clean and dry.
6, 7, 8 Tank interstitial sensor functional test not accomplished (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
8 Tank monitor does not appear to function properly and requires maintenance. - Tank 8 premium did not shown up on Veeder Root when I first printed inventory and testing from Veeder Root. I went through the Veeder Root and reprinted the inventory and testing and all three tanks printed properly. Contractor

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
00-0797 5/1/2000 Removal Log 03525-1999REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
89-0365 Eligible 5/9/1996 5/30/1996 $50,000
00-0797 Eligible 8/15/2000 8/31/2000 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 9520 Gasoline Removed Federal $0.00 05/01/2000 - REM
2 9520 Gasoline Removed Federal $0.00 05/01/2000 - REM
3 9520 Gasoline Removed Federal $0.00 05/01/2000 - REM
4 550 Used Oil Removed Federal $0.00 03/13/1989 - REM
5 1000 Kerosene Removed Federal $0.00 03/13/1989 - REM
6 10000 Gasoline - Regular Currently in use Federal $0.00
7 6000 Gasoline - Regular Currently in use Federal $0.00
8 4000 Gasoline - Premium Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active

MFD Motorfuel Dispensing Forms