Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2016458
Status: Active
Facility Name: Galena Shell
Address: 320 West Galena Boulevard
Aurora, IL 605064028
County: Kane
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X003202
Green Tag Issue Date: 6/15/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Hanif Malik
Owner Address: 905 W. Illinois
Aurora, IL 60506
Owner Status: Current Owner
Purchase Date: 8/30/2001
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 5/8/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 3/11/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0029619 Malik, Hanif Current Owner 8/30/2001
U0013849 Shell Oil Products Former Owner 10/15/1993
U0027449 Equilon Enterprises, LLC Former Owner 6/13/1981
U0000651 B.A.P.A., LLC & PT, LLC Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020240858 (Pending)    Issue Date: 3/21/2024    Expiration Date: 5/20/2024    View NOV Form

Tanks Deficiency
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain on site with other annual testing documentation.
5, 6, 7 Document that emergency shut-off (shear valves) are in proper working order - Provide documentation that annual testing of all shear valves has been conducted and passed.
6, 7 Miscellaneous - Tank 6 and 7 interstitial sensor is in alarm (L6). Repair must be made and alarm cleared.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and documentation maintained on site.
5, 6, 7 Monthly line interstitial sensor records not available. - Monthly normal line sensor report must be kept.
5, 6, 7 Precision line test required. - Since monthly normal sensor reports were not all kept a precision line test is required.
5, 6, 7 Precision tank test required. - Since monthly normal sensor reports were not all kept a precision tank test is required.
5, 6, 7 Required monthly tank interstitial sensor records not available. - Monthly normal tank sensor reports must be kept.
5, 6, 7 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Spill Bucket(s) contain(s) liquid and/or debris; remove liquid/debris and maintain clean and dry at all times.
5, 6, 7 Tank monitor does not appear to function properly and requires maintenance. - Veeder Root is in alarm (Fuel Alarm L1, L3, and L6). All alarms must be repaired so ATG is clear of all alarms.
5, 7 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - STP sump(s) contain(s) liquid, creating alarm on ATG. Remove liquid and repair containment to prevent further liquid ingress. Repair/replace sensor(s) as necessary to clear alarm.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
01-0835 5/15/2001 Removal Log 02244-2000REM

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline Removed Federal $0.00 05/15/2001 - REM
2 10000 Gasoline Removed Federal $0.00 05/15/2001 - REM
3 8000 Gasoline Removed Federal $0.00 05/15/2001 - REM
4 8000 Gasoline Removed Federal $0.00 05/15/2001 - REM
5 12000 Gasoline - Regular Currently in use Federal $0.00
6 6000 Gasoline - Regular Currently in use Federal $0.00
7 6000 Gasoline - Premium Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active

MFD Motorfuel Dispensing Forms

No Forms Found