Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2016439
Status: Active
Facility Name: Gurnee Truck Stop
Address: 36725 N. US 41
Gurnee, IL 60031
County: Lake
Property Parcel: 07-10-200-009
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X003088
Green Tag Issue Date: 12/7/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Gurnee Truck Stop, Inc.
Owner Address: 36725 N US Hwy 41, Unit A
Gurnee, IL 60031
Owner Status: Current Owner
Purchase Date: 2/18/2004
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 9/21/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 12/7/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040721 Gurnee Truck Stop, Inc. Current Owner 2/18/2004
U0032072 Chummar, Thomas Former Owner 6/1/2006
U0022147 Wisconsin North, L.L.C. Former Owner 2/24/2004
U0000651 B.A.P.A., LLC & PT, LLC Former Owner 12/31/1967
U0022147 Wisconsin North, L.L.C. Former Owner
U0027936 Wisconsin North, LLC Former Operator

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020240480 (Pending)    Issue Date: 2/21/2024    Expiration Date: 4/21/2024    View NOV Form

Tanks Deficiency
7 Annual electronic line leak detector test not completed.
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
5, 6, 7 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
5, 6 Annual line precision and mechanical line leak detector functional test not completed.
7 Dispensers - hose breakaways are missing or leaking - Hose breakaways should be tightened.
7 Dispensers - hoses cracked, split or worn and require replacement - Cracked hose.
5, 6, 7 Line interstitial sensor functional test not accomplished (Required annually).
5, 6, 7 Line interstitial sensors have been raised and rendered inoperational. - (STP/UDC) Interstitial sensor(s) are not functioning effectively. Place sensors vertically at the lowest point in the sump. (Per 175.410. 2.A.ii) (Check all dispensers)
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at www.sfm.illinois.gov. The form must be filled out by an A/B Operator, you must, initial each box that applies, date the form each month to ensure it is being done every 30 days, and the A/B operator must print and sign their name at the bottom. If more than one A/B operator fills out the form, then each must print and sign name at the bottom.
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing copies of current testing certificates for operator training - Missing certifications for all C Operators.
5, 6, 7 Monthly line interstitial sensor records not available. - Maintain one NORMAL report per LINE, per month, from ATG. (Liquid Status)
5, 6, 7 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
5, 6, 7 Triennial spill prevention equipment testing not completed.
5, 6, 7 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Triennial testing for qualifying STP/dispenser piping containment sump(s) not completed. Testing shall be completed and submitted to OSFM.
7 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - STP sump(s) contain(s) liquid. Remove liquid and repair containment to prevent further liquid ingress.
7 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Truck island UDC sump(s) contain(s) liquid. Remove liquid and repair containment to prevent further liquid ingress.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
05-1201 8/25/2005 Removal Log 00805-2005REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
99-1928 Eligible 11/30/1999 12/10/1999 $10,000
05-1201 Eligible 12/7/2012 12/28/2012 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 8000 Diesel Fuel Removed Federal $0.00 08/25/2005 - REM
2 8000 Gasoline Removed Federal $0.00 08/25/2005 - REM
3 8000 Gasoline Removed Federal $0.00 08/25/2005 - REM
4 8000 Gasoline Removed Federal $0.00 08/25/2005 - REM
5 10000 Gasoline - Premium Currently in use Federal $0.00
6 20000 Gasoline - Regular Currently in use Federal $0.00
7 20000 Diesel Fuel Currently in use Federal $0.00
8 10000 100% Soy Oil (Non-Regulated) Unknown Non-Regulated $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active
13/14 Active
15/16 Active
17/18 Active
19/20 Active
21/22 Active
23/24 Active
D1 Active
D2 Active
D3 Active
D4 Active
D4S Active

MFD Motorfuel Dispensing Forms

No Forms Found