| 8, 9 |
Failed to Empty the Tank to 1" or Less - Per 175.810(a) (1), when placing tanks out of service, the tanks and lines must be emptied immediately. The UST is considered empty when all materials have been removed to one inch or less. |
| 8, 9 |
Spill prevention equipment failed triennial testing. Must be repaired or replaced. - Triennial inspection/testing of spill bucket(s) has failed. Repair/replace as necessary; devices shall be retested with passing results. |
| 8, 9 |
Submit Notification Form For Tank Status Change - Per 175.810(a) (3), tanks taken out of service are required to notify the OSFM within 30 days of the date of last use, on an electronic Notification for Underground Storage Tank form, declaring a tank status change. Here is the link to the electronic Notification for Underground Storage Tank form, so you can file that change: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. |