Deficiencies (Current)
NOV Number:
E0020240924
(Pending)
Issue Date:
3/29/2024
Expiration Date:
5/28/2024
View NOV Form
Tanks |
Deficiency |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. |
NOV Number:
E0020240925
(Pending)
Issue Date:
3/29/2024
Expiration Date:
5/28/2024
View NOV Form
Tanks |
Deficiency |
7, 8, 9 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Triennial inspection of overfill device (overfill alarm) has not been completed. Testing shall be completed with passing results and uploaded to OSFM website. |
8, 9 |
Precision tank test required. - Precision tank test is required on tanks. |
7, 8, 9 |
Required monthly tank leak test records not available. - Maintain one PASSing report per TANK, per month, from ATG. Must maintain 24 months’ worth. If you cannot keep enough product in your tanks, you must upgarde your automatic tank gauge to read at a lower level. |