Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2015079
Status: Active
Facility Name: Crystal Lake Mobil Mart, Inc.
Address: 451 Virginia Street
Crystal Lake, IL 60014
County: McHenry
Property Parcel: 19-06-280-012
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X003368
Green Tag Issue Date: 9/16/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Omni Petroleum, Inc.
Owner Address: 451 W. Virginia Street
Crystal Lake, IL 60014
Owner Status: Current Owner
Purchase Date: 6/23/2019
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 4/3/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 5/10/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039925 Omni Petroleum, Inc. Current Owner 6/23/2019
U0038343 Abdul Hamid Patel Former Owner 1/1/2015
U0033800 Singh, Sawaran Former Owner 8/1/2006
U0001775 Boncosky Oil Company Former Owner 9/20/1994
U0009491 M&R Trust Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00348-2024UPG Upgrade Approved / Issued 3/28/2024 3/28/2024 9/30/2024 Documents

Deficiencies (Current)

NOV Number: E0020240498 (Pending)    Issue Date: 2/22/2024    Expiration Date: 4/22/2024    View NOV Form

Tanks Deficiency
6, 7, 8 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Section 175.410 Submersible, Under-dispenser, Transition and Other Containment Sumps a) All containment sumps must consist of a factory manufactured containment that is liquid-tight on its sides, bottom and at any penetrations and is compatible with the substance conveyed by the piping. Such containment shall also have a factory manufactured protective cover and supporting components that are properly maintained. If the protective cover or its supporting components are cracked, deteriorated or missing, the cover and supporting components that are defective shall be replaced. Tank 6 missing/broken vapor recovery lid, currently has a cone over it. Replace lid. Tanks 7 & 8 repair or replace STP lid handles.
6, 7 Open electrical conduit or junction boxes. - JUNCTION BOX AT ATG MANWAY IS BROKEN WITH EXPOSED WIRING. REPLACE JUNCTION BOX AND REPAIR WIRING.
4, 5, 6, 7, 8 Overfill alarm does not appear to function properly. - Overfill alarm is not functional, audible alarm is not working; repair/replace as necessary to insure functionality.
4 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.

NOV Number: E0020240499 (Pending)    Issue Date: 2/22/2024    Expiration Date: 4/22/2024    View NOV Form

Tanks Deficiency
Facility Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser - Section 175.210g; All dispensing units shall be readily visible from the control station without assistive devices. If view is permanently obstructed, or the dispenser is located so that activity is not readily visible, closed-circuit cameras that provide a view of each side of the dispensing unit and project an image on a screen at least 6 inches in diagonal located at the control station may be used. There is no view of the Dispensers 9/10 or 11 for the racing fuel or diesel.
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
97-0950 Eligible 9/9/1997 9/22/1997 $15,000
97-0950 Ineligible 3/3/2009 3/26/2009 $Not Selected
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 8000 Gasoline Removed Federal $0.00 01/01/1988 - REM
2 8000 Gasoline Removed Federal $0.00 01/01/1988 - REM
3 3000 Gasoline Removed Federal $0.00 01/01/1988 - REM
4 8000 Diesel Fuel Currently in use Federal 4/29/2024 $0.00
5 1000 Racing Fuel Currently in use Federal 4/29/2024 $0.00
6 10000 Gasoline - Premium Currently in use Federal 4/29/2024 $0.00
7 10000 Gasoline - Regular Currently in use Federal 4/29/2024 $0.00
8 10000 Gasoline - Regular Currently in use Federal 4/29/2024 $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11 Active

MFD Motorfuel Dispensing Forms

No Forms Found