Deficiencies (Current)
NOV Number:
E0020240191
(Pending)
Issue Date:
1/23/2024
Expiration Date:
3/23/2024
View NOV Form
Tanks |
Deficiency |
6, 8 |
Line leak detection equipment in alarm or failed test, must repair or replace. - L4 And L7 are in alarm. |
3, 5, 6, 7, 8 |
Tank monitor does not appear to function properly and requires maintenance. - Indicator light(s) on panel of Veeder-Root ATG is/are not functional. Replace as necessary to provide proper operation. (Red Yellow and Green out) |
9 |
Tank monitor does not appear to function properly and requires maintenance. - Stick product readings and stick water readings due not match Tank monitor readings. |
6 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - (Regular South STP) |