Facility Number: 2014700
Status: Inactive
Facility Name: Conoco Phillips 66
Address: 11957 - 11959 S. Halsted
Chicago, IL 60628
County: Cook
Property Parcel: 25-28-100-011-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Q003638
Green Tag Issue Date: 11/20/2015
Green Tag Expiration Date: 12/31/2017

Owner Details

Owner Name: Sandhu Petroleum Corporation Number 2
Owner Address: 301 N. Hough Street
Barrington, IL 60010
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance and Trust Fund
Financial Responsibility Reporting Due Date: 11/22/2014

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 11/20/2015 12/31/2017

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0024145 Sandhu Petroleum Corporation Number 2 Current Owner
U0017400 Phillips 66 Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020171434 (Pending)    Issue Date: 5/4/2017    Expiration Date: 7/3/2017    View NOV Form

Tanks Deficiency
1, 2, 3, 6, 7 Annual line precision and mechanical line leak detector functional test not completed.
1, 2, 3 Annual tank impressed current system appears not to be operational. - Last Test in system shows 11-4-2015
1, 2, 3, 6, 7 Document that emergency shut-off (shear valves) are in proper working order
1, 2, 3, 6, 7 Failed to Empty the Tank to 1" or Less
Facility Financial responsibility must be reported yearly
6, 7 Precision tank test required.
1, 2, 3 Remove tank(s) - Corrosion Protection not Maintained
1, 2, 3, 6, 7 Required monthly tank leak test records not available.
1, 2, 3, 6, 7 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
1, 2, 3, 6, 7 Submit Notification Form For Tank Status Change

NOV Number: E0020240128 (Pending)    Issue Date: 1/11/2024    Expiration Date: 3/11/2024    View NOV Form

Tanks Deficiency
Facility Financial responsibility must be reported yearly - 41 Ill. Adm. Code Section 176.245 Release from the Requirements An owner or operator is no longer required to maintain financial responsibility pursuant to this Subpart for a UST after the UST has been removed or abandoned-in-place, in accordance with 41 Ill. Adm. Code 175.830 and 175.840. https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility
6, 7 Submit Notification Form For Tank Status Change - OSFM must receive a written request, within 30 days after the date the tank was last used, requesting an out of service status. The request shall be submitted on a Notification for Underground Storage Tanks on OSFM forms (available athttps://sfm.illinois.gov/about/divisions/petroleum-chemical-safety/applications-and-forms.html).

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
04-1362 12/1/2004 Removal Log 108213

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
04-1132 Eligible 2/7/2005 3/4/2005 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 6000 Gasoline Condemned Tank Federal 5/4/2017 $0.00
2 6000 Gasoline Condemned Tank Federal 5/4/2017 $0.00
3 6000 Gasoline Condemned Tank Federal 5/4/2017 $0.00
4 1000 Kerosene Removed Federal $0.00 12/01/2004 - REM
5 1000 Kerosene Removed Federal $0.00 12/01/2004 - REM
6 1500 Diesel Fuel Out of service Federal 5/4/2017 $0.00
7 1500 Kerosene Out of service Federal 5/4/2017 $0.00

Dispenser Information

Name\ID Status

MFD Motorfuel Dispensing Forms