Deficiencies (Current)
NOV Number:
E0020241277
(Pending)
Issue Date:
5/1/2024
Expiration Date:
6/30/2024
View NOV Form
Tanks |
Deficiency |
Facility |
Code complying instruction/warning signs are not properly mounted at each dispenser island - 175.210 Attended self-service motor fuel dispensing facilities and islands O) Minimum signage 1), 2), 3), 4), and 5). Warning signs are required at all dispensers. |
NOV Number:
E0020241278
(Pending)
Issue Date:
5/1/2024
Expiration Date:
6/30/2024
View NOV Form
Tanks |
Deficiency |
Facility |
Miscellaneous - Emergency shut off switch at control station requires a sign. Lettering must be 2" in height. Stating "Emergency Stop" |
1, 2, 3, 4 |
Shear valve(s) not in proper working order. - Contractor that performed annual walkthrough failed shear valves for not working properly. Repair must be made and then passed by contractor. |
1, 2, 3, 4 |
Shear valve(s) not properly mounted and/or not at proper height. - Contractor that performed annual walkthrough failed shear valves for improper height. Shear valves must be within 1/2" of grade. Repair must be made to adjust height of shear valves and passed by contractor. |
1, 2, 3, 4 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Spill buckets must be kept clean and dry. |