Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2012725
Status: Active
Facility Name: Minuteman Citgo
Address: 205 N. Main Street
Wauconda, IL 60084
County: Lake
Property Parcel: 09-26-404-026
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X003082
Green Tag Issue Date: 12/1/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Exron Capitol, Inc.
Owner Address: 3340 S. Harlem Ave.
Riverside, IL 60546
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Designated Savings Account
Financial Responsibility Reporting Due Date: 2/9/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 12/1/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0036308 Exron Capitol, Inc. Current Owner
U0014941 Texor Petroleum Company, Inc. Former Owner 3/12/2002
U0014781 Sweeney Oil Co Former Owner 11/1/1981

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241019 (Pending)    Issue Date: 4/8/2024    Expiration Date: 6/7/2024    View NOV Form

Tanks Deficiency
9 Flex connector sacrificial anode system not tested (required every 3 years) - Test anodes and replace as needed - Three-year third-party testing required on sacrificial anode/cathodic protection system. Perform testing and maintain passing documentation on site for review by OSFM Inspector.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at www.sfm.illinois.gov. The form must be filled out by an A/B Operator, you must, initial each box that applies, date the form each month to ensure it is being done every 30 days, and the A/B operator must print and sign their name at the bottom. If more than one A/B operator fills out the form, then each must print and sign name at the bottom.
7, 8, 9 Monthly line interstitial sensor records not available. - Maintain one NORMAL report per LINE, per month, from ATG. (Liquid Status)
7, 8, 9 Required monthly tank leak test records not available. - Maintain one PASSing report per TANK, per month, from ATG. (CSLD)
7, 8, 9 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
9 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - STP Sump requires testing.
7, 8 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - STP sump(s) contain(s) liquid. Remove liquid and repair containment to prevent further liquid ingress.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
98-2286 2/8/1999 Removal Log 4492-98

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
98-2286 Eligible 5/3/1999 5/18/1999 $10,000
98-2286 Returned 4/17/2008 5/9/2008 $Not Selected
98-2286 Eligible 7/3/2013 8/8/2013 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 4000 Gasoline Removed Federal $0.00 02/08/1999 - REM
2 4000 Gasoline Removed Federal $0.00 02/08/1999 - REM
3 4000 Diesel Fuel Removed Federal $0.00 02/08/1999 - REM
4 4000 Gasoline Removed Federal $0.00 02/08/1999 - REM
5 1000 Heating Oil Removed State $0.00 02/08/1999 - REM
6 550 Used Oil Removed Exempt 02/08/1999 - REM
7 8000 Gasoline - Premium Currently in use Federal $0.00
8 12000 Gasoline - Regular Currently in use Federal $0.00
9 8000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

No Forms Found