Deficiencies (Current)
NOV Number:
E0020240997
(Pending)
Issue Date:
4/4/2024
Expiration Date:
6/3/2024
View NOV Form
Tanks |
Deficiency |
Facility |
Fire Extinguishers - Past due for annual testing - Fire extinguishers shall be provided in accordance with 41 IL Adm. Code 174.350. |
NOV Number:
E0020240998
(Pending)
Issue Date:
4/4/2024
Expiration Date:
6/3/2024
View NOV Form
Tanks |
Deficiency |
Facility |
Miscellaneous - Vapor caps are missing and broken for all three tanks. Replace vapor caps. |
5, 6, 7 |
Piping interstitial must be open in all sumps - 175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps. |
5, 6, 7 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Spill buckets must remain clean and dry. |