Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2010079
Status: Active
Facility Name: Bensenville Shell
Address: 600 IL Route 83
Bensenville, IL 60106
County: Du Page
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X000770
Green Tag Issue Date: 4/19/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Kaloco Oil Company
Owner Address: 1440 Renaissance Dr.
Suite 260
Park Ridge, IL 60068
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Letter of Credit
Financial Responsibility Reporting Due Date: 6/12/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 4/19/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0011937 Kaloco Oil Company Current Owner
U0032660 Kaloco Oil Company Former Owner 11/20/2003
U0029789 Clark Retail Enterprises, Inc. Former Owner 9/2/2003
U0003073 Clark Retail Enterprises, Inc. Former Owner 11/22/1988
U0028787 Clark Retail Enterprises, Inc., Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241079 (Pending)    Issue Date: 4/11/2024    Expiration Date: 6/10/2024    View NOV Form

Tanks Deficiency
8, 10, 11 Annual electronic line leak detector test not completed. - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Emergency shutoff switch shall be installed and located so that at least one emergency shutoff is at least 20 feet but not more than 100 feet from each dispenser.
8, 10, 11 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
8, 10, 11 Document that emergency shut-off (shear valves) are in proper working order - Provide documentation that annual testing of all shear valves has been conducted and passed.
11 Miscellaneous - ATG shows diesel has 28 gallons and 1.34" of water in tank.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and documentation maintained on site.
8, 10, 11 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Triennial inspection/testing of overfill prevention device (overfill drop tube valve, and/or overfill alarm, and/or ball float valve) has not been completed. Testing shall be completed with passing results.
8, 10, 11 Precision tank test required.
8, 10, 11 Required monthly tank leak test records not available. - Maintain one passing report per tank, per month, from ATG.
8, 10, 11 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Spill Bucket(s) contain(s) liquid and/or debris; remove liquid/debris and maintain clean and dry at all times.
8, 10, 11 Triennial spill prevention equipment testing not completed. - Triennial inspection/testing of spill bucket(s) has not been completed. Testing shall be completed with passing results.
10, 11 Water in containment without required interstitial sensors - install cathodic protection on all exposed steel. - Submersible sump(s) contain liquid which is corroding the exposed steel. Install approved cathodic protection to prevent further corrosion of submersible pump and related piping components.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
89-1080 Eligible 5/20/2003 6/19/2003 $50,000
89-1080 Eligible 9/17/2012 11/14/2012 $50,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 7500 Gasoline Removed Federal $0.00 01/01/1988 - REM
2 7500 Gasoline Removed Federal $0.00 01/01/1988 - REM
3 7500 Gasoline Removed Federal $0.00 01/01/1988 - REM
4 10000 Gasoline Removed Federal $0.00 09/01/1989 - REM
5 10000 Gasoline Removed Federal $0.00 09/01/1989 - REM
6 500 Removed Exempt 10/05/1989 - REM
7 500 Removed Exempt 10/05/1989 - REM
8 10000 Gasoline - Premium Currently in use Federal $0.00
10 10000 Gasoline - Regular Currently in use Federal $0.00
11 10000 B-11 Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active

MFD Motorfuel Dispensing Forms

No Forms Found