Deficiencies (Current)
NOV Number:
E0020241034
(Pending)
Issue Date:
4/9/2024
Expiration Date:
6/8/2024
View NOV Form
Tanks |
Deficiency |
3 |
Annual electronic line leak detector test not completed. |
Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. |
3, 4 |
Annual leak detection certification not completed (Required annually). |
Facility |
Missing copies of Annual Walkthrough Inspection Report. |
3, 4 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). |
3, 4 |
Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). |
3, 4 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
NOV Number:
E0020241036
(Pending)
Issue Date:
4/9/2024
Expiration Date:
6/8/2024
View NOV Form
Tanks |
Deficiency |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable |