Deficiencies (Current)
NOV Number:
E0020150918
(Referred to Legal)
Issue Date:
4/9/2015
Expiration Date:
6/8/2015
View NOV Form
Tanks |
Deficiency |
1, 2, 3 |
Annual tank impressed current system appears not to be operational. - All Power to Rectifier has been turned off. |
1, 2, 3 |
Failed to Empty the Tank to 1" or Less |
Facility |
Financial responsibility must be reported yearly - Financial Responsibility shall be declared annually; declaration form left on site. Complete form and mail to highlighted address at top of form. |
1, 2, 3 |
Flex connector sacrificial anode system not tested (required every 3 years) - Test anodes and replace as needed - Three-year third party testing required on sacrificial anode/cathodic protection system. Perform annual testing and maintain passing documentation on site for review by OSFM Inspector. |
1, 2, 3 |
Monthly impressed current system log not available or maintained. - A log showing the rectifier gauge readings from Impressed Current rectifier shall be maintained monthly on site for review by OSFM Inspector. Log shall show date; amp, volt and hour meter readings; who recorded information. |
Facility |
Submit Notification Form For Ownership Change - Submit OSFM Notification Form showing change in facility ownership. Notification form is available at www.sfm.illinois.gov |
1, 2, 3 |
Submit Notification Form For Tank Status Change - Submit OSFM Notification Form placing all tanks in Temporarily Out of Use status. Notification form is available at www.sfm.illinois.gov |
NOV Number:
E0020160119
(Formal)
Issue Date:
1/20/2016
Expiration Date:
3/20/2016
View NOV Form
Tanks |
Deficiency |
1, 2, 3 |
Remove tank(s) - Corrosion Protection not Maintained |
1, 2, 3 |
Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year |
NOV Number:
E0020170928
(Formal)
Issue Date:
3/27/2017
Expiration Date:
5/26/2017
View NOV Form
Tanks |
Deficiency |
1, 2, 3 |
Remove tank(s) - Corrosion Protection not Maintained |
1, 2, 3 |
Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year |
NOV Number:
E0020170929
(Formal)
Issue Date:
3/27/2017
Expiration Date:
5/26/2017
View NOV Form
Tanks |
Deficiency |
1, 2, 3 |
Remove tank(s) - Corrosion Protection not Maintained |
1, 2, 3 |
Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year |