Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2009901
Status: Inactive
Facility Name: Broadway Clark
Address: 619 S. Broadway St.
Aurora, IL 60505
County: Kane
Property Parcel: 15-28-282-023
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: W004053
Green Tag Issue Date: 7/27/2021
Green Tag Expiration Date: 10/19/2023

Owner Details

Owner Name: Arif Shiekh
Owner Address: 619 South Broadway
Aurora, IL 60505
Owner Status: Current Owner
Purchase Date: 3/1/2006
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 7/26/2022

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 7/27/2021 12/31/2023

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0033778 Shiekh, Arif Current Owner 3/1/2006
U0032118 Virinda Corp. Former Owner 3/1/2006
U0032118 Virinda Corp. Former Owner 9/1/2003
U0029789 Clark Retail Enterprises, Inc. Former Owner 11/22/1988
U0003073 Clark Retail Enterprises, Inc. Former Owner 11/22/1988
U0028787 Clark Retail Enterprises, Inc., Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020230968 (Referred to Legal)    Issue Date: 4/19/2023    Expiration Date: 6/18/2023    View NOV Form

Tanks Deficiency
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain on site with other annual testing documentation.
1 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
1 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
2 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
2 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
3 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
3 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
1, 2, 3 Annual tank impressed current system test not completed. - Annual third-party testing required on impressed current system. Perform annual testing and maintain passing documentation on site for review by OSFM Inspector. Impressed current must be maintained even if tanks are out of service.
1, 2, 3 Document that emergency shut-off (shear valves) are in proper working order - Provide documentation that annual testing of all shear valves has been conducted and passed.
1, 2, 3 Failed to Empty the Tank to 1" or Less - All tanks must be pumped down to one inch or less.
Facility Financial responsibility must be reported yearly - Financial Responsibility shall be declared annually; declaration form can be found at www.sfm.illinois.gov Complete form online and submit electronically.
1, 2, 3 Impressed current system failed test or appears non operational. Must repair. - There is no power going to impressed current. Impressed current must be maintained even if tanks are out of service.
1, 2, 3 Line interstitial sensor functional test not accomplished (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at www.sfm.illinois.gov
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and documentation maintained on site.
1, 2, 3 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Triannual testing of ball floats not complete. Test and enter passing date in portal.
1, 2, 3 Precision line test required.
1, 2, 3 Precision tank test required.
1, 2, 3 Required monthly tank leak test records not available. - Maintain one PASSing report per TANK, per month, from ATG.
1, 2, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Spill Bucket(s) contain(s) liquid and/or debris; remove liquid/debris and maintain clean and dry at all times.
1, 2, 3 Submit Notification Form For Tank Status Change - A notification form must be completed taking tanks out of service. Form can be found at https://sfm.illinois.gov/
1, 2, 3 Triennial spill prevention equipment testing not completed. - Triennial inspection/testing of spill bucket(s) has not been completed. Testing shall be completed with passing results.
1, 2, 3 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - STP sump needs triannual testing with a passing date entered on portal.

NOV Number: E0020230969 (Referred to Legal)    Issue Date: 4/19/2023    Expiration Date: 6/18/2023    View NOV Form

Tanks Deficiency
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable
Facility Fire Extinguishers - Minimum 4A:60BC are not present at each island and at an emergency shutoff switch

NOV Number: E0020232333 (Pending)    Issue Date: 10/19/2023    Expiration Date: 12/18/2023    View NOV Form

Tanks Deficiency
3 Failed to Empty the Tank to 1" or Less - Tank 3 premium still has 7" of product in it. Tank must be pumped down to 1" or less.
Facility Financial responsibility must be reported yearly - Financial Responsibility must be declared annually. The form can be found at: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility
1, 2, 3 Remove tank(s) - Corrosion Protection not Maintained - Tanks have been condemned and must be removed.
Facility Submit Notification Form For Ownership Change - The Notification Form is available at: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of an ownership change.
1, 2, 3 Submit Notification Form For Tank Status Change - The Notification Form is available at: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of a tank status change. Tanks must be changed to out of service.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
95-0180 Eligible 5/16/1995 5/30/1995 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 7500 Gasoline - Regular Condemned Tank Federal 4/19/2023 $0.00
2 7500 Gasoline - Regular Condemned Tank Federal 4/19/2023 $0.00
3 7500 Gasoline - Premium Condemned Tank Federal 4/19/2023 $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms