Deficiencies (Current)
NOV Number:
E0020241197
(Pending)
Issue Date:
4/22/2024
Expiration Date:
6/21/2024
View NOV Form
Tanks |
Deficiency |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom. 175.210 h) |
Facility |
LP gas storage lacks proper collision protection or a 40" measurement from cabinet to a 5" raised sidewalk - Provide appropriate collision protection for LP tank cage. Refer to OSFM Rules section 175.210 q) for proper placement of collision protection. |
NOV Number:
E0020241198
(Pending)
Issue Date:
4/22/2024
Expiration Date:
6/21/2024
View NOV Form
Tanks |
Deficiency |
Facility |
Electrical Does Not Comply - Regular west tank has open electric. A plug is missing from the junction box. |
2, 3 |
Line interstitial sensors have been raised and rendered inoperational. - Interstitial sensor(s) has/have been raised rendering it/them ineffective. Repair/replace sensor(s) into proper location so that it can function as designed. |
Facility |
Miscellaneous - Exterior Emergency Shut Off Switch is blocked with an ice cooler. E Stop needs to be free from obstructions. |
1, 2, 3 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Spill Bucket(s) contain(s) liquid and/or debris; remove liquid/debris and maintain clean and dry at all times. |
2, 3 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - STP sump(s) contain(s) liquid. Remove liquid and repair containment to prevent further liquid ingress. |