Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2009003
Status: Active
Facility Name: Citgo
Address: 6700 S. Jeffery Blvd.
Chicago, IL 60649
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002087
Green Tag Issue Date: 2/14/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Parkview Services, Inc.
Owner Address:
Owner Status: Current Owner
Purchase Date: 6/1/2014
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 1/18/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 2/8/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0032512 Parkview Services, Inc. Current Owner 6/1/2014
U0036296 Joman Thomas, Former Owner
U0010471 Exxon Mobil Oil Corporation Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

No Deficiencies Found

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
87-1729 Eligible 3/23/1994 4/5/1994 $50,000
20081701 Eligible 2/15/2018 3/2/2018 $10,000 Letter
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 40 Abandoned Date:
Install Date: 1/1/1984 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1984

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 9/13/2023 9/13/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 8/31/2023 8/31/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 9/12/2022 9/12/2023
Overfill Prev Device Overfill Drop Tube Valve 9/12/2022 9/12/2025
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 8/16/2021 8/16/2024
Leak Detect - Piping Sump Sensor 8/31/2023 8/31/2024
Spill Contain Device Single Wall Spill Bucket 8/16/2021 8/16/2024
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test Pass 9/13/2023



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 40 Abandoned Date:
Install Date: 1/1/1984 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1984

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 9/13/2023 9/13/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 8/31/2023 8/31/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 9/12/2022 9/12/2023
Overfill Prev Device Overfill Drop Tube Valve 9/12/2022 9/12/2025
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 8/16/2021 8/16/2024
Leak Detect - Piping Non-Discriminating Sump Sensor 8/16/2021 8/16/2022
Leak Detect - Piping Sump Sensor 8/31/2023 8/31/2024
Spill Contain Device Single Wall Spill Bucket 8/16/2021 8/16/2024
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test Pass 9/13/2023



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 40 Abandoned Date:
Install Date: 1/1/1984 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1984

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/31/2023 8/31/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 8/31/2023 8/31/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 9/12/2022 9/12/2023
Overfill Prev Device Overfill Drop Tube Valve 9/12/2022 9/12/2025
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 8/16/2021 8/16/2024
Leak Detect - Piping Sump Sensor 8/31/2023 8/31/2024
Spill Contain Device Single Wall Spill Bucket 8/16/2021 8/16/2024
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 40 Abandoned Date:
Install Date: 1/1/1984 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1984

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/31/2023 8/31/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 8/31/2023 8/31/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 9/12/2022 9/12/2023
Overfill Prev Device Overfill Drop Tube Valve 9/12/2022 9/12/2025
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 8/16/2021 8/16/2024
Leak Detect - Piping Non-Discriminating Sump Sensor 8/18/2020 8/18/2021
Leak Detect - Piping Sump Sensor 8/31/2023 8/31/2024
Spill Contain Device Single Wall Spill Bucket 8/16/2021 8/16/2024
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test Pass 8/19/2020

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/16/2021 8/16/2024
Leak Detect - Piping Sump Sensor 8/31/2023 8/31/2024



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/16/2021 8/16/2024
Leak Detect - Piping Sump Sensor 8/31/2023 8/31/2024



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/16/2021 8/16/2024
Leak Detect - Piping Sump Sensor 8/31/2023 8/31/2024



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/16/2021 8/16/2024
Leak Detect - Piping Sump Sensor 8/31/2023 8/31/2024



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/16/2021 8/16/2024
Leak Detect - Piping Sump Sensor 8/31/2023 8/31/2024

MFD Motorfuel Dispensing Forms

No Forms Found