Financial responsibility must be reported yearly - The Notification Form is available at: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of an ownership change. |
5 |
Line interstitial sensors have been raised and rendered inoperational. - Interstitial sensor(s) has/have been raised rendering it/them ineffective. Repair/replace sensor(s) into proper location so that it can function as designed. STP Sump |
2 |
Stick inserted in drop tube overfill device rendering it inoperative - Remove stick. - A tank depth gauge stick is in the drop tube: remove stick to maintain proper operation of drop tube valve. |
5 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - STP sump contains liquid. Remove liquid and repair containment to prevent further liquid ingress. |