Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2006999
Status: Active
Facility Name: Shell Station
Address: 1620 W. 127th Street
Calumet Park, IL 60643
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X002930
Green Tag Issue Date: 3/10/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: JBK Calumet Properties, Inc.
Owner Address: 1620 W. 127th Street
Calumet Park, IL 60645
Owner Status: Current Owner
Purchase Date: 3/21/2017
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 6/29/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 3/10/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039167 JBK Calumet Properties, Inc. Current Owner 3/21/2017
U0035735 True North Energy, LLC Former Owner 3/8/2010
U0027449 Equilon Enterprises, LLC Former Owner 1/1/1972
U0013849 Shell Oil Products Former Owner 12/31/1967
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241129 (Pending)    Issue Date: 4/16/2024    Expiration Date: 6/15/2024    View NOV Form

Tanks Deficiency
Facility Code complying instruction/warning signs are not properly mounted at each dispenser island - Minimum signage is not up to code. Reference 175.210 o) (Dispenser 7/8 missing signage.)
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable

NOV Number: E0020241130 (Pending)    Issue Date: 4/16/2024    Expiration Date: 6/15/2024    View NOV Form

Tanks Deficiency
Facility Facility Operation and Maintenance Plan not completed or available. - Facility Operations and Maintenance Plan is available at https://sfm.illinois.gov to download and complete. Maintain documentation on site
2 Install or replace lockable fill pipe caps. - Fill snap cap broke. Repair/Replace.
2 Line interstitial sensors have been raised and rendered inoperational. - Repair/replace sensor(s) into proper location so that it can function as designed. (Regular STP)
1, 2, 3 Miscellaneous - Tanks 1 & 2 lines are manifolded above shear valves and need to be verified that the shear valves are double poppeted.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at https://sfm.illinois.gov. (Not Complete)
1, 2, 3 Overfill prevention equipment inspection(s) not completed (Required every 3 years).
1, 2, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
2 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Regular STP.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
03-0441 Eligible 8/22/2003 9/2/2003 $10,000
09-0142 Eligible 4/21/2009 4/29/2009 $10,000
09-0142 Eligible 10/5/2011 12/4/2011 $10,000
03-0441 Eligible 10/5/2011 12/4/2011 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 52 Abandoned Date:
Install Date: 1/1/1972 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1972

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Lining Materials Internal 7/9/2019 7/9/2024
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/5/2023 6/5/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 6/5/2023 6/5/2024
Overfill Prev Device Overfill Drop Tube Valve 7/10/2019 7/10/2022
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 7/13/2021 7/13/2024
Leak Detect - Piping Sump Sensor 6/5/2023 6/5/2024
Spill Contain Device Single Wall Spill Bucket 7/13/2021 7/13/2024
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Precision Test Pass 5/23/2022
Tank Fiberglass Single Wall Precision Test (Tank) Pass 7/10/2019



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 52 Abandoned Date:
Install Date: 1/1/1972 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1972

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Lining Materials Internal 7/9/2019 7/9/2024
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Other Non-vented check valve N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 6/5/2023 6/5/2024
Overfill Prev Device Overfill Drop Tube Valve 7/10/2019 7/10/2022
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 7/13/2021 7/13/2024
Leak Detect - Piping Sump Sensor 6/5/2023 6/5/2024
Spill Contain Device Single Wall Spill Bucket 7/13/2021 7/13/2024
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Precision Test Pass 5/23/2022
Tank Fiberglass Single Wall Precision Test (Tank) Pass 7/10/2019



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 52 Abandoned Date:
Install Date: 1/1/1972 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1972

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Lining Materials Internal 7/9/2019 7/9/2024
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/5/2023 6/5/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 6/5/2023 6/5/2024
Overfill Prev Device Overfill Drop Tube Valve 7/10/2019 7/10/2022
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 7/13/2021 7/13/2024
Leak Detect - Piping Sump Sensor 6/5/2023 6/5/2024
Leak Detect - Piping Sump Sensor with positive shutdown 6/5/2023 6/5/2024
Spill Contain Device Single Wall Spill Bucket 7/13/2021 7/13/2024
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Precision Test Pass 5/23/2022
Tank Fiberglass Single Wall Precision Test (Tank) Pass 7/10/2019



Tank Number 4

Capacity: 1000 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/3/1994
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 22 Abandoned Date:
Install Date: 1/1/1972 Red Tag Issue Date:
Last Used Date: 3/31/1994 Fee Due: $0.00
Product Date: 1/1/1972

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found