Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2006999
Status: Active
Facility Name: Shell Station
Address: 1620 W. 127th Street
Calumet Park, IL 60643
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X002930
Green Tag Issue Date: 3/10/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: JBK Calumet Properties, Inc.
Owner Address: 1620 W. 127th Street
Calumet Park, IL 60645
Owner Status: Current Owner
Purchase Date: 3/21/2017
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 6/29/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 3/10/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039167 JBK Calumet Properties, Inc. Current Owner 3/21/2017
U0035735 True North Energy, LLC Former Owner 3/8/2010
U0027449 Equilon Enterprises, LLC Former Owner 1/1/1972
U0013849 Shell Oil Products Former Owner 12/31/1967
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241129 (Pending)    Issue Date: 4/16/2024    Expiration Date: 6/15/2024    View NOV Form

Tanks Deficiency
Facility Code complying instruction/warning signs are not properly mounted at each dispenser island - Minimum signage is not up to code. Reference 175.210 o) (Dispenser 7/8 missing signage.)
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable

NOV Number: E0020241130 (Pending)    Issue Date: 4/16/2024    Expiration Date: 6/15/2024    View NOV Form

Tanks Deficiency
Facility Facility Operation and Maintenance Plan not completed or available. - Facility Operations and Maintenance Plan is available at https://sfm.illinois.gov to download and complete. Maintain documentation on site
2 Install or replace lockable fill pipe caps. - Fill snap cap broke. Repair/Replace.
2 Line interstitial sensors have been raised and rendered inoperational. - Repair/replace sensor(s) into proper location so that it can function as designed. (Regular STP)
1, 2, 3 Miscellaneous - Tanks 1 & 2 lines are manifolded above shear valves and need to be verified that the shear valves are double poppeted.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at https://sfm.illinois.gov. (Not Complete)
1, 2, 3 Overfill prevention equipment inspection(s) not completed (Required every 3 years).
1, 2, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
2 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Regular STP.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
03-0441 Eligible 8/22/2003 9/2/2003 $10,000
09-0142 Eligible 4/21/2009 4/29/2009 $10,000
09-0142 Eligible 10/5/2011 12/4/2011 $10,000
03-0441 Eligible 10/5/2011 12/4/2011 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline - Regular Currently in use Federal $0.00
2 10000 Gasoline - Regular Currently in use Federal $0.00
3 8000 Gasoline - Premium Currently in use Federal $0.00
4 1000 Used Oil Removed Federal $0.00 05/03/1994 - REM

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

No Forms Found