Deficiencies (Current)
NOV Number:
E0020240800
(Pending)
Issue Date:
3/18/2024
Expiration Date:
5/17/2024
View NOV Form
Tanks |
Deficiency |
Facility |
LP gas storage lacks proper collision protection or a 40" measurement from cabinet to a 5" raised sidewalk - PLEASE HAVE BOLLARDS PLACED IN FRONT OF AND ON THE NORTH SIDE OF THE LP TANKS CAGE |
NOV Number:
E0020240801
(Pending)
Issue Date:
3/18/2024
Expiration Date:
5/17/2024
View NOV Form
Tanks |
Deficiency |
1, 2, 3 |
Annual electronic line leak detector test not completed. - LAST TESTED 6-11-22 |
1, 2, 3 |
Annual leak detection certification not completed (Required annually). - LAST TESTED 6-11-22 |
Facility |
Missing copies of 30 day Walkthrough Inspection Report. |
Facility |
Missing copies of Annual Walkthrough Inspection Report. |
1, 2, 3 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). - LAST TEST WAS 5-14-20 AND 9-11-20 |
1, 2, 3 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
1, 2, 3 |
Triennial spill prevention equipment testing not completed. - LAST TEST WAS 5-14-20 AND 9-11-20 |