Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2000474
Status: Active
Facility Name: IDOT Interstate 55 (137)
Address: 151 E. South Frontage Road
Bolingbrook, IL 60439
County: Will
Property Parcel: 00000000
Facility Type: State
Owner Type: State
Green Tag Decal: X000288
Green Tag Issue Date: 9/16/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Illinois Department of Transportation
Owner Address: 2300 S. Dirksen Parkway
Springfield, IL 62764
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 12/27/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 9/16/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0021798 Illinois Department of Transportation Current Owner
U0007359 Il Dept of Transportation District 1 Former Owner 6/22/1995

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

No Deficiencies Found

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 6/22/1995
OSFM First Notify Date: 12/31/1987 Abandoned Material:
Current Age: 11 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/11/1995 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: 6/22/1995 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 6/22/1995

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 12/5/2023 12/5/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS - 4c 12/5/2023 12/5/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/5/2023 12/5/2024
Overfill Prev Device Overfill Drop Tube Valve 7/19/2022 7/19/2025
Piping Polyethylene Chase N/A N/A
Piping Flexible Double Wall A.P.T. Poly Tech S150SC N/A N/A
Piping Single Wall STP/Tanktop Sump 7/19/2022 7/19/2025
Leak Detect - Piping Sump Sensor with positive shutdown 12/5/2023 12/5/2024
Spill Contain Device Single Wall Spill Bucket 7/19/2022 7/19/2025
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Chase Secondary Containment A.P.T. Poly Tech DCT-400 Precision Test Pass 4/30/2020
Piping Flexible Double Wall A.P.T. Poly Tech S150SC Precision Test Pass 12/5/2023
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive Precision Test Pass 10/18/2019

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/19/2022 7/19/2025
Leak Detect - Piping Sump Sensor with positive shutdown 12/5/2023 12/5/2024

MFD Motorfuel Dispensing Forms

No Forms Found