Deficiencies (Current)
NOV Number:
E0020240603
(Pending)
Issue Date:
3/1/2024
Expiration Date:
4/30/2024
View NOV Form
Tanks |
Deficiency |
Facility |
Miscellaneous - EMERGENCY STOP SWITCH NOT PROPERLY MARKED AND NOT EASILY ACCESSIBLE. PLACE PROPER SIGNAGE/PLACARD AT SWITCH AND CLEAR THE AREA SO THE SWITCH IS EASILY ACCESSIBLE TO ATTENDANT. |
1, 2, 3 |
Precision tank test required. - Precision tank test is required on tank(s) if you cannot provide 24 months’ worth of tank “PASS” from ATG. |
1, 2, 3 |
Required monthly tank leak test records not available. - Maintain one PASSing report per TANK, per month, from ATG. Must maintain 24 months’ worth. Missing Oct, Nov, Dec of 2023 & Jan, Feb of 2024. |
NOV Number:
E0020240604
(Pending)
Issue Date:
3/1/2024
Expiration Date:
4/30/2024
View NOV Form
Tanks |
Deficiency |
Facility |
Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser - Section 175.210g; All dispensing units shall be readily visible from the control station without assistive devices. If view is permanently obstructed, or the dispenser is located so that activity is not readily visible, closed-circuit cameras that provide a view of each side of the dispensing unit and project an image on a screen at least 6 inches in diagonal located at the control station may be used. are not visible from Control Station. In lieu of cameras, Remove impediments from windows or install remote cameras to monitor dispenser activity. |
Facility |
Code complying instruction/warning signs are not properly mounted at each dispenser island - Self-service instructional signs at dispensers are missing or do not meet minimum requirements. Install appropriate signage. Signs must be visible to each dispenser. |
Facility |
Miscellaneous - LP GAS STORAGE LESS THAN 5 FEET FROM WINDOW |