Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 1047054
Status: Active
Facility Name: Eagle Ridge Inn & Resort
Address: 444 Eagle Ridge Drive
Galena, IL 61036
County: Jo Daviess
Property Parcel: 08-900-305-06
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X003922
Green Tag Issue Date: 1/10/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Eagle Ridge Inn & Resort
Owner Address: PO Box 777
Galena, IL 61036
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 7/25/2023

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/10/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0023514 Eagle Ridge Inn & Resort Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020240636 (Pending)    Issue Date: 3/5/2024    Expiration Date: 5/4/2024    View NOV Form

Tanks Deficiency
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain on site with other annual testing documentation
1, 2 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (ATG) not completed.
1, 2 Annual line precision and mechanical line leak detector functional test not completed. - Annual third party testing required on all line leak detectors.
Facility Financial responsibility must be reported yearly - Financial Responsibility shall be declared annually; declaration form can be found at www.sfm.illinois.gov (in Search window, type UST Forms, Click Enter; click UST Applications and Forms; click on Financial Responsibility Report). Complete form online and submit electronically.
1, 2 Line interstitial sensor functional test not accomplished (Required annually). - Annual third party testing required on all line interstitial sensors.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed and documentation maintained on site.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and documentation maintained on site
Facility Missing copies of current testing certificates for operator training - Copies of all current Class A/B testing certificates shall be maintained on file on site. Copies of all current Class C testing certificates shall be maintained on file on site.
1, 2 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Triennial inspection of overfill prevention device (overfill drop tube valve,) has not been completed.
1, 2 Tank interstitial sensor functional test not accomplished (Required annually). - Annual third party testing required on all tank interstitial sensors.
1, 2 Triennial spill prevention equipment testing not completed. - Triennial inspection of spill bucket(s) has not been completed.
1, 2 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Triennial testing for qualifying STP piping containment sump(s) not completed. Triennial testing for qualifying dispenser containment sump(s) not completed.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 2000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/6/2020 Abandoned Material:
Current Age: 3 Abandoned Date:
Install Date: 5/18/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/22/2020

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Jacketed Steel Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 12/9/2021 12/9/2022
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 12/9/2021 12/9/2022
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/9/2021 12/9/2022
Overfill Prev Device Overfill Drop Tube Valve 7/17/2020 7/17/2023
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 6/1/2020 6/1/2023
Leak Detect - Piping Sump Sensor with positive shutdown 12/9/2021 12/9/2022
Spill Contain Device Double Wall Spill Bucket 6/1/2020 6/1/2023
Tank Composite Double Wall Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 2000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/6/2020 Abandoned Material:
Current Age: 3 Abandoned Date:
Install Date: 5/18/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/22/2020

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Jacketed Steel Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 12/9/2021 12/9/2022
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 12/9/2021 12/9/2022
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/9/2021 12/9/2022
Overfill Prev Device Overfill Drop Tube Valve 7/17/2020 7/17/2023
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 6/1/2020 6/1/2023
Leak Detect - Piping Sump Sensor with positive shutdown 12/9/2021 12/9/2022
Spill Contain Device Double Wall Spill Bucket 6/1/2020 6/1/2023
Tank Composite Double Wall Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/1/2020 6/1/2023
Leak Detect - Piping Sump Sensor with positive shutdown 12/9/2021 12/9/2022



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/1/2020 6/1/2023
Leak Detect - Piping Sump Sensor with positive shutdown 12/9/2021 12/9/2022

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
1047054 Eagle Ridge Inn & Resort Galena 05/14/2020 Letter Form