Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 1046980
Status: Active
Facility Name: Speedway #1144
Address: 2001 Walnut Street
Oglesby, IL 61348
County: LaSalle
Property Parcel: 18-34-212-000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X002868
Green Tag Issue Date: 12/21/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Speedway, LLC
Owner Address: P.O. Box 1500
Springfield, OH 45501
Owner Status: Current Owner
Purchase Date: 7/15/2019
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/13/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 6/2/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0026552 Speedway, LLC Current Owner 7/15/2019
U0039647 DO NOT USE THIS OWNER ID - Speedway, LLC Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020240943 (Pending)    Issue Date: 4/1/2024    Expiration Date: 5/31/2024    View NOV Form

Tanks Deficiency
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Emergency shutoff switch shall be tested annually. Perform test, complete testing form (form is available at www.sfm.illinois.gov) and maintain on site with other annual testing documentation
Facility Facility Operation and Maintenance Plan not completed or available. - Adopt and implement a written operations and maintenance plan, signed by both the owner and either a Class A or Class B Operator designated for the UST facility An Operations & Maintenance template is available on the OSFM website.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and documentation maintained on site
Facility Missing copies of current testing certificates for operator training - Copies of all current Class A/B testing certificates shall be maintained on file on site. Copies of all current Class C testing certificates shall be maintained on file on site. Go to www.sfm.illinois.gov (UST Operator Training) to find current information regarding Operator. Training requirements, including all relevant forms.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures plan shall be maintained on site for viewing and reference as necessary (See Operator Training Rules 176.645). The emergency plan template is available on the OSFM website.
Facility Missing list of designated Class A/B & C Operators - A comprehensive list of Class A / B / C Operator(s) shall be maintained on site Left Copy onsite
1, 2, 3, 4, 5, 6 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed.
Facility Submit Notification Form for Facility Information Change - The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of an ownership/operator change.

NOV Number: E0020240987 (Pending)    Issue Date: 4/4/2024    Expiration Date: 6/3/2024    View NOV Form

Tanks Deficiency
5 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Top lid steel ring is bent making removal for inspection difficult. Repair.
5, 6 Line interstitial sensors have been raised and rendered inoperational. - Under Dispensor sensors have been raised on Dispensor 17, 17 satellite, 18, 19 and 19 satellite.
Facility Miscellaneous
Facility Missing copies of 30 day Walkthrough Inspection Report.
1, 2, 3, 4, 5, 6 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
5, 6 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Dispensor 17, 17 satellite, 18, 19 and 19 satellite, have liquid in containment.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 6000 Gasoline - Premium Currently in use Federal $0.00
2 6000 E85 Currently in use Federal $0.00
3 12000 B-11 Currently in use Federal $0.00
4 20000 Gasoline - Regular Currently in use Federal $0.00
5 20000 Diesel Fuel Currently in use Federal $0.00
6 20000 Diesel Fuel Currently in use Federal $0.00
7 10000 Diesel Exhaust Fluid (Non-Regulated) Unknown Non-Regulated $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
7/8 Active
20 Active
19 Active
9/10 Active
5/6 Active
11/12 Active
13/14 Active
15/16 Active
17 Active
18 Active
19S Active

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
1046980 Speedway #1144 Oglesby 08/10/2020 Letter Form