Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 1046532
Status: Active
Facility Name: Circle K #1474
Address: 2301 S. Perryville Rd.
Rockford, IL 61108
County: Winnebago
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X003032
Green Tag Issue Date: 5/13/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Mac's Convenience Stores, LLC
Owner Address: 1100 Situs Court, Suite 100
Raleigh, NC 27606
Owner Status: Current Owner
Purchase Date: 12/21/2017
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/27/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 5/13/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0030949 Mac's Convenience Stores, LLC Current Owner 12/21/2017
U0035671 RDK Ventures, LLC Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020240940 (Pending)    Issue Date: 4/1/2024    Expiration Date: 5/31/2024    View NOV Form

Tanks Deficiency
1, 2, 3, 4 Annual electronic line leak detector test not completed. - Annual third party testing required on all line leak detectors.
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain on site with other annual testing documentation.
1, 2, 3, 4 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (ATG) not completed.
1, 2, 3, 4 Line interstitial sensor functional test not accomplished (Required annually). - Annual third party testing required on all line interstitial sensors.
1, 2, 3, 4 Tank interstitial sensor functional test not accomplished (Required annually). - Annual third party testing required on all tank interstitial sensors.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/29/2018 Abandoned Material:
Current Age: 6 Abandoned Date:
Install Date: 12/21/2017 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/22/2018

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/4/2024 3/4/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 3/4/2024 3/4/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/4/2024 3/4/2025
Manway At Grade Accessible Manway Accessible at Grade N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 3/4/2024 3/4/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 12/13/2021 12/13/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025
Spill Contain Device Double Wall Spill Bucket 3/4/2024 3/4/2027
Tank Fiberglass Double Wall Containment Solutions N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 3/4/2024



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/29/2018 Abandoned Material:
Current Age: 6 Abandoned Date:
Install Date: 12/21/2017 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/22/2018

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/4/2024 3/4/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 3/4/2024 3/4/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/4/2024 3/4/2025
Manway At Grade Accessible Manway Accessible at Grade N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 3/4/2024 3/4/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 12/13/2021 12/13/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025
Spill Contain Device Double Wall Spill Bucket 3/4/2024 3/4/2027
Tank Fiberglass Double Wall Containment Solutions N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 3/4/2024



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/29/2018 Abandoned Material:
Current Age: 6 Abandoned Date:
Install Date: 12/21/2017 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/22/2018

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/4/2024 3/4/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 3/4/2024 3/4/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/4/2024 3/4/2025
Manway At Grade Accessible Manway Accessible at Grade N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 3/4/2024 3/4/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 12/13/2021 12/13/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025
Spill Contain Device Double Wall Spill Bucket 3/4/2024 3/4/2027
Tank Fiberglass Double Wall Containment Solutions N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 3/4/2024



Tank Number 4

Capacity: 15000 Petroleum Use:
Product: Gasoline - Non Ethanol CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/29/2018 Abandoned Material:
Current Age: 6 Abandoned Date:
Install Date: 12/21/2017 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/22/2018

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/4/2024 3/4/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 3/4/2024 3/4/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/15/2024 3/15/2025
Manway At Grade Accessible Manway Accessible at Grade N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 3/4/2024 3/4/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 12/13/2021 12/13/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025
Spill Contain Device Double Wall Spill Bucket 3/4/2024 3/4/2027
Tank Fiberglass Double Wall Containment Solutions N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 3/4/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/13/2021 12/13/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/13/2021 12/13/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/13/2021 12/13/2024
Leak Detect - Piping Sump Sensor with positive shutdown 4/4/2024 4/4/2025



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/13/2021 12/13/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 17/18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/13/2021 12/13/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 19/20

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/13/2021 12/13/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 21/22

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/13/2021 12/13/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 23/24

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/13/2021 12/13/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/13/2021 12/13/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/13/2021 12/13/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/13/2021 12/13/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/13/2021 12/13/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
1046532 Circle K #1474 Rockford 11/28/2017 Letter Form