Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 1042457
Status: Active
Facility Name: Murphy USA #7165
Address: 1620 South Galena Avenue
Highway 26
Dixon, IL 61021
County: Lee
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X002813
Green Tag Issue Date: 3/17/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Murphy Oil USA, Inc.
Owner Address: 200 E. Peach Street
El Dorado, AR 71730
Owner Status: Current Owner / Operator
Purchase Date:
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 6/29/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 2/16/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0029289 Murphy Oil USA, Inc. Current Owner / Operator

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020240236 (Pending)    Issue Date: 1/30/2024    Expiration Date: 3/30/2024    View NOV Form

Tanks Deficiency
Facility Fire Extinguishers - Past due for annual testing

NOV Number: E0020240237 (Pending)    Issue Date: 1/30/2024    Expiration Date: 3/30/2024    View NOV Form

Tanks Deficiency
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 3 Dispensers - hoses cracked, split or worn and require replacement - Hose needs to be replaced due to cracks.
1, 2, 3 Document that emergency shut-off (shear valves) are in proper working order
1, 2, 3 Line interstitial sensors have been raised and rendered inoperational. - All UDC sensors have been raised.
Facility Miscellaneous - STP lids are missing handles and and iron rings are out of round making it difficult to remove wthout causing damage with crow bars (chipping the lids). Sumps could not be inspected. Ensure lids can be removed as designed of have a contractor arrange to meet the inspector onsite so inspection can occur.
Facility Missing copies of Annual Walkthrough Inspection Report.
1, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/25/2005 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 3/17/2005 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/26/2005

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/31/2023 7/31/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 7/31/2023 7/31/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 7/31/2023 7/31/2024
Overfill Prev Device Overfill Drop Tube Valve 9/21/2021 9/21/2024
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 9/21/2023 9/21/2026
Piping Single Wall STP/Tanktop Sump 9/21/2023 9/21/2026
Leak Detect - Piping Non-Discriminating Sump Sensor 9/21/2021 9/21/2022
Leak Detect - Piping Sump Sensor 7/31/2023 7/31/2024
Spill Contain Device Double Wall Spill Bucket 7/31/2023 7/31/2026
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test Pass 7/31/2023



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/25/2005 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 3/17/2005 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/26/2005

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/31/2023 7/31/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 7/31/2023 7/31/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 7/31/2023 7/31/2024
Overfill Prev Device Overfill Drop Tube Valve 9/21/2021 9/21/2024
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 9/21/2023 9/21/2026
Leak Detect - Piping Sump Sensor 7/31/2023 7/31/2024
Spill Contain Device Single Wall Spill Bucket 7/31/2023 7/31/2026
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test Pass 7/31/2023



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/25/2005 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 3/17/2005 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/26/2005

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/31/2023 7/31/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 7/31/2023 7/31/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 7/31/2023 7/31/2024
Overfill Prev Device Overfill Drop Tube Valve 9/21/2021 9/21/2024
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 9/21/2023 9/21/2026
Leak Detect - Piping Sump Sensor 7/31/2023 7/31/2024
Spill Contain Device Double Wall Spill Bucket 7/31/2023 7/31/2026
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test Pass 7/31/2023

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/21/2023 9/21/2026
Leak Detect - Piping Sump Sensor 7/31/2023 7/31/2024



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/21/2023 9/21/2026
Leak Detect - Piping Sump Sensor 7/31/2023 7/31/2024



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/21/2023 9/21/2026
Leak Detect - Piping Sump Sensor 7/31/2023 7/31/2024



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/21/2023 9/21/2026
Leak Detect - Piping Sump Sensor 7/31/2023 7/31/2024

MFD Motorfuel Dispensing Forms