Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 1039512
Status: Active
Facility Name: Ohio Filling Station
Address: 302 N. Main Street
Ohio, IL 61349
County: Bureau
Property Parcel:
Facility Type: Attended Self-Service/Unattended Self-Service
Owner Type: Private
Green Tag Decal: X002281
Green Tag Issue Date: 9/13/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Ohio Properties, LLC
Owner Address: P.O. Box 37
Ohio, IL 61349
Owner Status: Current Owner
Purchase Date: 2/15/2017
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 10/30/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Unattended Self Service 4/13/2022 12/31/2024
Self Service 1/31/2018 12/31/2020

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039024 Ohio Properties, LLC Current Owner 2/15/2017
U0029280 Ohio Home Oil Company Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241124 (Pending)    Issue Date: 4/15/2024    Expiration Date: 6/14/2024    View NOV Form

Tanks Deficiency
Facility Annual Fire Detection Test has not been performed - Due annually for all unattended facilities. Note: new canopy does not appear to have a fire detection sustem installed.

NOV Number: E0020241125 (Pending)    Issue Date: 4/15/2024    Expiration Date: 6/14/2024    View NOV Form

Tanks Deficiency
Facility A/B operator retraining required as a result of issuance of the Notice of Violation
Facility Emergency contact information for A/B & C Operators not posted at unmanned facility - A / B Operator name and contact information shall be conspicuously posted on site for immediate reference (at Unmanned Facility only). In lieu of A/B Operator name/number, 24-hour security contact info can be substituted.
Facility Facility Operation and Maintenance Plan not completed or available. - Update for new owner
Facility Financial responsibility must be reported yearly - After the corrected notification is filed re-submitt the Financial Responsibility.
Facility Missing copies of 30 day Walkthrough Inspection Report. - Correctly perform the 30 day inspections using the date of the inspection in the month box as well as fully identifying the AB opertor (name should mach the AB certificate), only inspecting items that are relevant to this store.
Facility Missing copy of emergency instructions or emergency procedures plan - Update for new owner
Facility Missing list of designated Class A/B & C Operators
1, 2 Required monthly tank leak test records not available.
Facility Submit Notification Form for Facility Information Change - Notification form was rejected by OSFM due company name not matching the deed. Please follow through with the corrections. In addition to the name change, IF the facility is not going to be operated as unattended, please make this change also. New canopy does not aprear to have a fire detection sysetem installed.
1, 2 Tank monitor does not appear to function properly and requires maintenance. - ATG is not properly programed to produce the tank test pass required every month.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/8/2000 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 3/9/2000 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/9/2000

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 5/26/2023 5/26/2026
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/26/2023 5/26/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300c 4/18/2024 4/18/2025
Overfill Prev Device Overfill Drop Tube Valve 5/27/2022 5/27/2025
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Flex Connector Steel N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/27/2022 5/27/2025
Tank Fiberglass Single Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Environ Geo Flex Precision Test Pass 5/26/2023



Tank Number 2

Capacity: 4000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/8/2000 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 3/9/2000 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/9/2000

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 5/26/2023 5/26/2026
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/26/2023 5/26/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300c 4/18/2024 4/18/2025
Overfill Prev Device Overfill Drop Tube Valve 9/9/2022 9/9/2025
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Flex Connector Steel N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 9/9/2022 9/9/2025
Tank Fiberglass Single Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Environ Geo Flex Precision Test Pass 5/26/2023

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms