Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain on site with other annual testing documentation |
1, 2 |
Annual leak detection certification not completed (Required annually). - Annual leak detection certification (ATG) not completed. |
1, 2 |
Annual line precision and mechanical line leak detector functional test not completed. - Annual third party testing required on all line leak detectors. |
Facility |
Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and documentation maintained on site. |
1, 2 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Triennial inspection of overfill prevention device (overfill drop tube valve, overfill alarm, ball float valve) has not been completed. |
1, 2 |
Triennial spill prevention equipment testing not completed. - Triennial inspection of spill bucket(s) has not been completed. |
1, 2 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Triennial testing for qualifying STP piping containment sump(s) not completed.
Triennial testing for qualifying dispenser containment sump(s) not completed. |