2, 3 |
Annual electronic line leak detector test not completed. |
Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. |
2, 3 |
Annual leak detection certification not completed (Required annually). |
2, 3 |
Line interstitial sensor functional test not accomplished (Required annually). |
Facility |
Miscellaneous - Tank pad could not be inspected due to vehicles and boats on the tank pad. Please ensure area is clear when inspector returns for reinspection. |
Facility |
Missing copies of Annual Walkthrough Inspection Report. |
2, 3 |
Monthly line interstitial sensor records not available. |
2, 3 |
Required monthly tank leak test records not available. |
2, 3 |
Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). |
2, 3 |
Tank interstitial sensor functional test not accomplished (Required annually). |
2 |
Tank monitor does not appear to function properly and requires maintenance. - Green light on ATG needs to be repaired or replaced. |
2 |
Tank monitor does not appear to function properly and requires maintenance. - Warning light was on. |
3 |
Tank monitor does not appear to function properly and requires maintenance. - Green light on ATG needs to be repaired or replaced. |
3 |
Tank monitor does not appear to function properly and requires maintenance. - Warning light was on. |
2, 3 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Transition sump contains water and sensor is not in alarm. |