Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 1024331
Status: Active
Facility Name: Mega Mart, LLC
Address: 818 S. 6th Street
Rockford, IL 61104
County: Winnebago
Property Parcel: 11-26-427-003
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X003541
Green Tag Issue Date: 5/31/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Hailey Ventures, LLC
Owner Address: 818 S. 6th Street
Rockford, IL 61104
Owner Status: Current Owner
Purchase Date: 8/26/2021
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 5/31/2023

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 5/31/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040548 Hailey Ventures, LLC Current Owner 8/26/2021
U0037119 Malik, Aysha Former Owner 8/13/2012
U0033383 HA Sunny Pantry, Inc. Former Owner 11/17/2003
U0014612 Rockford Stop-N-Go, Inc. - DO NOT USE THIS OWNER ID Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020240794 (Pending)    Issue Date: 3/15/2024    Expiration Date: 5/14/2024    View NOV Form

Tanks Deficiency
1, 2, 3 Annual electronic line leak detector test not completed. - Annual third party testing required on all line leak detectors.
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain on site with other annual testing documentation
1, 2, 3 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (ATG) not completed.
1, 2, 3 Annual tank impressed current system test not completed. - Annual third party testing required on impressed current system
Facility Financial responsibility must be reported yearly - Financial Responsibility shall be declared annually; declaration form can be found at www.sfm.illinois.gov (in Search window, type UST Forms, Click Enter; click UST Applications and Forms; click on Financial Responsibility Report). Complete form online and submit electronically.
1, 2, 3 Line interstitial sensor functional test not accomplished (Required annually). - Annual third party testing required on all line interstitial sensors.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed and documentation maintained on site.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and documentation maintained on site.
Facility Missing copies of current testing certificates for operator training - Copies of all current Class A/B testing certificates shall be maintained on file on site. Copies of all current Class C testing certificates shall be maintained on file on site.
1, 2, 3 Monthly impressed current system log not available or maintained. - A log showing the rectifier gauge readings from Impressed Current rectifier shall be maintained monthly on site for review by OSFM Inspector. Log shall show date; amp, volt and hour meter readings; name of employee who recorded information.
1, 2, 3 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Triennial inspection of overfill prevention device (overfill drop tube valve, overfill alarm, ball float valve) has not been completed.
1, 2, 3 Required monthly tank leak test records not available. - Maintain one PASSing report per TANK, per month, from ATG.
1, 2, 3 Triennial spill prevention equipment testing not completed. - iennial inspection of spill bucket(s) has not been completed.
1, 2, 3 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Triennial testing for qualifying STP piping containment sump(s) not completed. Triennial testing for qualifying dispenser containment sump(s) not completed

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
98-0979 Eligible 11/9/1998 1/7/1999 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/23/1988 Abandoned Material:
Current Age: 34 Abandoned Date:
Install Date: 1/1/1988 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 11/22/2021 11/22/2022
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/27/2024 3/27/2025
Leak Detect - Tank Automatic Tank Gauging Gilbarco EMC with CSLD 3/27/2024 3/27/2025
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Alarm 3/27/2024 3/27/2027
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 4/23/2024 4/23/2027
Leak Detect - Piping Sump Sensor 4/23/2024 4/23/2025
Spill Contain Device Single Wall Spill Bucket 4/23/2024 4/23/2027
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Precision Test Pass 8/13/2020



Tank Number 2

Capacity: 6000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/23/1988 Abandoned Material:
Current Age: 34 Abandoned Date:
Install Date: 1/1/1988 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 11/22/2021 11/22/2022
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/27/2024 3/27/2025
Leak Detect - Tank Automatic Tank Gauging Gilbarco EMC with CSLD 3/27/2024 3/27/2025
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Alarm 3/27/2024 3/27/2027
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 4/23/2024 4/23/2027
Leak Detect - Piping Sump Sensor 11/22/2021 11/22/2022
Spill Contain Device Single Wall Spill Bucket 4/23/2024 4/23/2027
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 6000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/23/1988 Abandoned Material:
Current Age: 34 Abandoned Date:
Install Date: 1/1/1988 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 11/22/2021 11/22/2022
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/27/2024 3/27/2025
Leak Detect - Tank Automatic Tank Gauging Gilbarco EMC with CSLD 3/27/2024 3/27/2025
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Alarm 3/27/2024 3/27/2027
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 4/23/2024 4/23/2027
Leak Detect - Piping Sump Sensor 4/23/2024 4/23/2025
Spill Contain Device Single Wall Spill Bucket 4/23/2024 4/23/2027
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Precision Test Pass 8/13/2020

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/7/2020 10/7/2023
Leak Detect - Piping Sump Sensor 4/23/2024 4/23/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/7/2020 10/7/2023
Leak Detect - Piping Sump Sensor 4/23/2024 4/23/2025

MFD Motorfuel Dispensing Forms