Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 1015662
Status: Active
Facility Name: Express Lane Shell
Address: 1801 Locust Street
Sterling, IL 61081
County: Whiteside
Property Parcel: 11-16-378-013
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X000228
Green Tag Issue Date: 3/28/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Arthur J. Johnson Family Limited Partnership
Owner Address: 1305 12th Avenue
Rock Falls, IL 61071
Owner Status: Current Owner
Purchase Date: 10/19/2006
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 10/20/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 3/28/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040750 Arthur J. Johnson Family Limited Partnership Current Owner 10/19/2006
U0008040 Johnson Oil Company Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241183 (Pending)    Issue Date: 4/16/2024    Expiration Date: 6/15/2024    View NOV Form

Tanks Deficiency
Facility Fire Extinguishers - Past due for annual testing - 2/2023

NOV Number: E0020241185 (Pending)    Issue Date: 4/16/2024    Expiration Date: 6/15/2024    View NOV Form

Tanks Deficiency
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
Facility Facility Operation and Maintenance Plan not completed or available.
Facility Missing copies of 30 day Walkthrough Inspection Report.
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing list of designated Class A/B & C Operators
7 Required monthly tank interstitial sensor records not available.
5, 7 Required monthly tank leak test records not available.
5, 7 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
5, 7 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
5, 7 Tank precision test required.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
03-0736 5/19/2003 Removal Log 02440-2003REM
2023-0557 8/9/2023 Abandonment Log 00781-2023ABN
2023-0557 8/14/2023 Removal Log 00780-2023REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
03-0736 Eligible 2/10/2004 2/23/2004 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/19/2003
OSFM First Notify Date: 4/8/1986 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 5/19/2003 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/19/2003
OSFM First Notify Date: 4/8/1986 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 5/19/2003 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 6/15/1991
OSFM First Notify Date: 4/8/1986 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 6/1/1991 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Abandoned in place CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/20/1987 Abandoned Material: Inert material mixed with portland cement
Current Age: 36 Abandoned Date: 8/9/2023
Install Date: 11/3/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Sacrificial Anode Cathodic Protection 8/7/2020 8/7/2023
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 9/3/2022 9/3/2023
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 9/3/2022 9/3/2023
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Alarm 7/23/2021 7/23/2024
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 8/13/2020 8/13/2023
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test Pass 9/3/2022



Tank Number 5

Capacity: 4000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/30/2003 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: 5/20/2003 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/20/2003

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 9/28/2023 9/28/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 9/28/2023 9/28/2024
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Alarm 9/28/2023 9/28/2026
Piping Polyethylene Chase N/A N/A
Piping Flexible Double Wall OPW Flexworks N/A N/A
Piping Single Wall STP/Tanktop Sump 8/29/2023 8/29/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/28/2023 9/28/2024
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Double Wall Spill Bucket 8/29/2023 8/29/2026
Tank Composite Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test Pass 9/3/2022
Piping Flexible Double Wall OPW Flexworks Precision Test Pass 9/28/2023
Tank Composite Double Wall Precision Test (Tank) Pass 8/25/2020



Tank Number 6

Capacity: 4000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Abandoned in place CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/30/2003 Abandoned Material: Inert material mixed with portland cement
Current Age: 21 Abandoned Date: 8/9/2023
Install Date: 5/20/2003 Red Tag Issue Date:
Last Used Date: 10/5/2020 Fee Due: $0.00
Product Date: 5/20/2003

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 8/7/2020 8/7/2023
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 9/3/2022 9/3/2023
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 9/3/2022 9/3/2023
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Alarm 7/23/2021 7/23/2024
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 8/13/2020 8/13/2023
Tank Composite Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test Pass 9/3/2022
Tank Composite Double Wall Precision Test (Tank) Pass 8/25/2020



Tank Number 7

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/25/2023 Abandoned Material:
Current Age: 0 Abandoned Date:
Install Date: 7/28/2023 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 9/28/2023 9/28/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 9/28/2023 9/28/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 9/28/2023 9/28/2024
Overfill Prev Device Overfill Alarm 9/28/2023 9/28/2026
Piping Polyethylene Chase N/A N/A
Piping Flexible Double Wall OPW Flexworks N/A N/A
Piping Single Wall STP/Tanktop Sump 8/29/2023 8/29/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/28/2023 9/28/2024
Spill Contain Device Double Wall Spill Bucket 8/29/2023 8/29/2026
Tank Fiberglass Double Wall Fluid Containment Brine Filled N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Flexworks Precision Test Pass 9/28/2023
Tank Fiberglass Double Wall Fluid Containment Brine Filled Precision Test (Tank) Pass 9/28/2023



Tank Number 8

Capacity: 575 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 8/14/2023
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/31/1973 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 9

Capacity: 1000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 8/14/2023
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/31/1973 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 10

Capacity: 550 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 8/14/2023
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/31/1973 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 11

Capacity: 550 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 8/14/2023
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/31/1973 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/29/2023 8/29/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/28/2023 9/28/2024



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/29/2023 8/29/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/28/2023 9/28/2024



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/29/2023 8/29/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/28/2023 9/28/2024



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/29/2023 8/29/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/28/2023 9/28/2024

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
1015662 Express Lane Shell Sterling 09/22/2023 Letter Form