Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 1014347
Status: Active
Facility Name: Casey's General Store #1293
Address: 317 Pine Street
Buda, IL 61314
County: Bureau
Property Parcel: 14-34-356-013
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X002841
Green Tag Issue Date: 4/28/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Casey's Retail Company
Owner Address: 3305 SE Delaware Ave.
P.O. Box 3004
Ankeny, IA 50021
Owner Status: Current Owner
Purchase Date: 6/24/1986
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 10/27/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 4/28/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0002560 Casey's Retail Company Current Owner 6/24/1986

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
01273-2023UPG Upgrade Approved / Issued 11/2/2023 11/2/2023 5/2/2024 Documents
00414-2024CAT Cathodic Protection Cancelled by Contractor 4/12/2024 4/13/2024 10/16/2024 Documents

Deficiencies (Current)

NOV Number: E0020240853 (Pending)    Issue Date: 3/18/2024    Expiration Date: 5/17/2024    View NOV Form

Tanks Deficiency
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
Facility Missing copies of current testing certificates for operator training - A comprehensive list of Class A / B / C Operator(s) shall be maintained on site.
Facility Missing list of designated Class A/B & C Operators
1, 2 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
1, 2 Tank monitor does not appear to function properly and requires maintenance. - Indicator light(s) on panel of Veeder-Root ATG is/are not functional. Replace as necessary to provide proper operation. Green light is out.
1, 2 Water in containment without required interstitial sensors - install cathodic protection on all exposed steel. - Under dispenser containment sumps contain liquid which is corroding the exposed steel. Install approved cathodic protection to prevent further corrosion of dispenser piping and related piping components. Alternatively, repair containment to prevent water ingress.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
01-2068 Eligible 7/12/2002 8/1/2002 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline - Regular Currently in use Federal $0.00
2 6000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active

MFD Motorfuel Dispensing Forms

No Forms Found